Basler Electric DGC-2020 User Manual

Page 187

Advertising
background image

stability is further controlled by two timers. Voltage conditions must meet the stability pickup and dropout
settings for the duration of the Bus Stable Activation Delay

R

. Breaker closure is not considered if the

voltage conditions do not meet the stability pickup and dropout settings for the duration of the Bus Stable
Activation Delay setting. When the bus does not meet the voltage or frequency criteria for the Bus Stable
condition, the bus status is reported as Bus Failed (not stable and not dead) after the duration of the Bus
Failed Activation Delay

S

.

The Bus Stable overvoltage and undervoltage detection elements have the low-line scale factor

T

applied

to them to enhance versatility for reconfigurable machines. When the low-line override is active, the
thresholds for the overvoltage and undervoltage detection are multiplied by the low-line scale factor. The
effect is that low-line threshold = element threshold setting x low-line scale factor.

An alternate frequency scale factor setting

U

is used for automatic adjustment of the frequency pickup

settings in applications that might utilize more than one operating frequency. For example, a machine that
is configurable between 50 or 60 Hz operation. The scale factor setting is implemented when the DGC-
2020 senses a contact closure at a contact input that is connected to the Alternate Frequency Override
logic element in BESTlogicPlus Programmable Logic. When the Alternate Frequency Override is true, the
scale factor setting serves as a multiplier for the pickup settings. For example, if a scale factor contact
input is received by the DGC-2020 and the scale factor setting is 2.000, the pickup setting will be doubled
(2.000 x PU).

Settings which are related to machine ratings can be set in either actual units of voltage or in per unit

V

values. When a native unit is edited, BESTCOMSPlus automatically recalculates the per unit value based
on the native unit setting and the rated data parameter (on the System Parameters, Rated Data screen)
associated with it. When a per-unit value is edited, BESTCOMSPlus automatically recalculates the native
value based on the per unit setting and the rated data parameter associated with it.

Once all per unit values are assigned, if the rated data parameters are changed, BESTCOMSPlus
automatically recalculates all native unit settings based on the modified rated data parameters.

The following settings have native units of Primary Volts, and the rated data associated with them is
Rated Volts (on the System Parameters, Rated Data screen).

Dead Bus Threshold

Bus Stable Overvoltage Pickup

Bus Stable Overvoltage Dropout

Bus Stable Undervoltage Pickup

Bus Stable Undervoltage Dropout

The following settings have native units of Frequency in Hz, and the rated data associated with them is
Rated Frequency (on the System Parameters, Rated Data screen).

Bus Stable Overfrequency Pickup

Bus Stable Overfrequency Dropout

Bus Stable Underfrequency Pickup

Bus Stable Underfrequency Dropout

The BESTCOMSPlus Bus Condition Detection screen is illustrated in Figure 4-63.

NOTE

Voltage threshold and pickup settings on the Bus Condition Detection screen
are entered in primary values (generator side of VT).

9400200990 Rev X

DGC-2020 BESTCOMSPlus

® Software

4-77