Basler Electric DGC-2020 User Manual
Page 235

Name
Description
Symbol
Status Input
In Resting State
True when the DGC-2020 is in the resting state.
Status Input
In Running State
True when the DGC-2020 is in the running state.
Status Input
Lamp Test
True when the Lamp Test logic element is true or the
Lamp Test button is pressed on the front panel.
Status Input
Load Share
Module
Load Share Module AVR Output Limit. True when
the LSM-2020 AVR Output Limit settings have been
exceeded.
Status Input
Load Share
Module
Load Share Module Connected. True when an
optional LSM-2020 is connected to the DGC-2020.
Status Input
Load Share
Module
Load Share Module Governor Output Limit. True
when the LSM-2020 Governor Output Limit settings
have been exceeded.
Status Input
Load Take Over
True when the Load Take Over logic element is true.
Status Input
Low Line
Override
True when the Low Line Override input is true.
Status Input
Mains Breaker
Status
True when the mains breaker is closed.
Status Input
Mains Fail Test
True when the Mains Fail Test logic element is true.
Status Input
Mains Fail
Transfer
Complete
True when the DGC-2020 is configured for mains fail
transfers and has successfully transferred to the
generator from the utility. It remains true until the
utility power is deemed good and the DGC-2020
transfers the load back to utility power.
Status Input
Off Mode
True when the DGC-2020 is in Off Mode or the Off
Mode logic element is true.
Status Input
Off Mode
Cooldown
True when the DGC-2020 is in Off Mode and cooling
down.
Status Input
Parallel To Mains
True when the Parallel To Mains logic element is
true, indicating that the generator is operating in
parallel with the utility.
Status Input
PF Mode Active
True when PF mode is active.
Status Input
Pre Start
Condition in
Effect
True while in the Pre Start state.
Status Input
Pre Start Input
True when the DGC-2020 is indicating that the Pre
Start relay should be closed.
9400200990 Rev X
DGC-2020 BESTlogic
™
Plus Programmable Logic
5-7