Register

Description

Type

Units

Scaling

Factor

R/W

Range

44756

Gen VAN Metering

Int32

Volt

N/A

R

(-2147483648) - 2147483647

44758

Gen VBN Metering

Int32

Volt

N/A

R

(-2147483648) - 2147483647

44760

Gen VCN Metering

Int32

Volt

N/A

R

(-2147483648) - 2147483647

44762

Bus Voltage Metering

Int32

Volt

N/A

R

(-2147483648) - 2147483647

44764

Gen IA Metering

Int32

Amp

N/A

R

(-32768) - 32767

44766

Gen IB Metering

Int32

Amp

N/A

R

(-32768) - 32767

44768

Gen IC Metering

Int32

Amp

N/A

R

(-32768) - 32767

44770

Gen kVA A Metering

Int32

KiloVA

N/A

R

(-2147483648) - 2147483647

44772

Gen kVA B Metering

Int32

KiloVA

N/A

R

(-2147483648) - 2147483647

44774

Gen kVA C Metering

Int32

KiloVA

N/A

R

(-2147483648) - 2147483647

44776

Gen kVA Total Metering

Int32

KiloVA

N/A

R

(-2147483648) - 2147483647

44778

Gen kW A Metering

Int32

KiloWatt

N/A

R

(-2147483648) - 2147483647

44780

Gen kW B Metering

Int32

KiloWatt

N/A

R

(-2147483648) - 2147483647

44782

Gen kW C Metering

Int32

KiloWatt

N/A

R

(-2147483648) - 2147483647

44784

Gen kW Total Metering

Int32

KiloWatt

N/A

R

(-2147483648) - 2147483647

44786

Power Factor Metering

Float

N/A

N/A

R

(-1) - 1

44788

Gen PF Lagging

Int32

N/A

N/A

R

0 = leading, 1 = lagging

44790

Gen Frequency
Metering

Float

Hertz

N/A

R

45 - 440

44792

Bus Frequency Metering

Float

Hertz

N/A

R

45 - 440

44794

Active Speed Source

Uint32

N/A

N/A

R

0 = None
1 = MPU
2 = Gen Freq
4 = CAN bus

44796

Engine Speed Metering

Uint32

RPM

N/A

R

0 - 65535

44798

Engine Load Metering

Int32

Percent

N/A

R

(-32768) - 32767

44800

Coolant Temp. Metering

Int32

Deg F

N/A

R

(-32768) - 32767

44802

Oil Pressure Metering

Int32

PSI

N/A

R

(-32768) - 32767

44804

Battery Voltage
Metering

Int32

DeciVolt

N/A

R

(-32768) - 32767

44806

Fuel Level Metering

Int32

N/A

N/A

R

(-32768) - 32767

44808

ECU Coolant Level
Metering

Uint32

N/A

N/A

R

0 - 255

44810

Cool Down Time
Remaining

Int32

Minute

N/A

R

(-128) - 127