Engine kW Over
Load 3

True when the Engine kW Overload 3 Pre-Alarm
settings have been exceeded.

Fuel Leak

True when the Fuel Leak Detect function is
configured as a pre-alarm and the activation delay
has expired.

Fuel Level
Sender Fail

True when the Fuel Level Sender Fail is configured
as a pre-alarm and the activation delay has expired.

Generator
Breaker Close
Fail

True when a generator breaker close fail pre-alarm
occurs. The pre-alarm occurs when the DGC-2020
has issued a generator breaker close output but
does not receive a generator breaker status input
that indicates the breaker has closed before the
breaker close wait time has expired.

Generator
Breaker Open
Fail

True when a generator breaker open fail pre-alarm
occurs. The pre-alarm occurs when the DGC-2020
has issued a generator breaker open output but does
not receive a generator breaker status input that
indicates the breaker has opened before the breaker
close wait time has expired.

Generator
Breaker Sync
Fail

True when a generator breaker sync fail pre-alarm
occurs. The pre-alarm occurs when the synchronizer
is running and attempting to close the generator
breaker but the sync fail activation delay expires prior
to achieving breaker closure.

Generator
Protection

27-1

True when the 27-1 element is configured as a pre-
alarm and has tripped.

Generator
Protection

27-2

True when the 27-2 element is configured as a pre-
alarm and has tripped.

Generator
Protection

59-1

True when the 59-1 element is configured as a pre-
alarm and has tripped.

Generator
Protection

59-2

True when the 59-2 element is configured as a pre-
alarm and has tripped.

Generator
Protection

32

True when the 32 element is configured as a pre-
alarm and has tripped.

Generator
Protection

40

True when the 40 element is configured as a pre-
alarm and has tripped.

Generator
Protection

47

True when the 47 element is configured as a pre-
alarm and has tripped.

Generator
Protection

51-1

True when the 51-1 element is configured as a pre-
alarm and has tripped.

Generator
Protection

51-2

True when the 51-2 element is configured as a pre-
alarm and has tripped.

5-14

DGC-2020 BESTlogic

Plus Programmable Logic