Speed bias, Voltage bias, Speed bias -7 – Basler Electric DGC-2020 User Manual

Page 361: Voltage bias -7

Advertising
background image

Synchronizer Active for a Short Time, Then Stops

Step 1: Check if a Sync Fail pre-alarm or a Breaker Close Fail pre-alarm is occurring or has occurred.

The synchronizer stops acting when such a pre-alarm occurs. Press the Off button or the Reset
button on the DGC-2020 front panel to clear these pre-alarms.

Step 2: Verify that the Sync Fail Activation delay is sufficiently long to allow the synchronizer to

complete the synchronization process.

Step 3: Verify that the Breaker Close Wait time is not too short causing a pre-alarm to occur before the

breaker closes when a breaker close is initiated by the DGC-2020.

Synchronizer Does Not Lower Engine Speed Allowing Alignment of Bus and Generator

Step 1: Using the front panel HMI, navigate to the SETTINGS > MULTIGEN MANAGEMENT > GOV

ANALOG OUTPUT screen and set SPD RESPONSE to DECREASING.

Synchronizer Does Not Raise Engine Speed Allowing Alignment of Bus and Generator

Step 1: Using the front panel HMI, navigate to the SETTINGS > MULTIGEN MANAGEMENT > GOV

ANALOG OUTPUT screen and set SPD RESPONSE to DECREASING.

Synchronizer Does Not Lower the Generator Voltage to Achieve Matching of Bus and Generator
Voltages

Step 1: Navigate to the SETTINGS > MULTIGEN MANAGEMENT > AVR ANALOG OUTPUT screen

and set VOLT RESPONSE to DECREASING.

Synchronizer Does Not Raise Generator Voltage to Achieve Matching of Bus and Generator
Voltages

Step 1: Navigate to the SETTINGS > MULTIGEN MANAGEMENT > AVR ANALOG OUTPUT screen

and set VOLT RESPONSE to DECREASING.

Speed Bias

Engine Speed Does Not Change When Speed Bias Voltage Changes

Step 1: Verify that the engine speed will change when the speed bias changes. As a test, you can force

a voltage on the speed bias output by setting the Min Output Voltage and Max Output Voltage
to the same value by navigating to SETTINGS > MULTIGEN MANAGEMENT > GOV ANALOG
OUPUT. If the bias is current based, you can force a fixed current by setting the Governor
Output Current Minimum and Maximum to the same value by navigating to SETTINGS >
MULTIGEN MANAGEMENT > GOV ANALOG OUTPUT.

If the speed still does not change when varying the bias:

•

Verify that the governor or ECU is equipped and configured to accept bias inputs.

•

Check connections to verify the wiring to the governor bias is correct.

•

If you have an engine with an ECU, check ECU programming to verify it is set up to
accept a speed bias input.

Engine Speed Decreases When Speed Bias is Increased

Step 1: Navigate to the SETTINGS > MULTIGEN MANAGEMENT > GOV ANALOG OUTPUT screen

and set SPD RESPONSE to DECREASING.

Engine Speed Increases When Speed Bias is Decreased

Step 1: Navigate to the SETTINGS > MULTIGEN MANAGEMENT > GOV ANALOG OUTPUT screen

and set SPD RESPONSE to DECREASING.

Voltage Bias

Generator Voltage Does Not Change When Voltage Bias Changes

Step 1: As a test, you can force a voltage on the AVR bias output by setting the Min Output Voltage

and Max Output Voltage to the same value by navigating to SETTINGS > MULTIGEN
MANAGEMENT > AVR OUTPUT. If the bias is current based, you can force a fixed current by
setting the Min Output Current and Max Output Current to the same value by navigating to
SETTINGS > MULTIGEN MANAGEMENT > AVR OUTPUT.

9400200990 Rev X

DGC-2020 Maintenance and Troubleshooting

8-7