9400200990 Rev X

DGC-2020 Modbus

™ Communication

B-81

Register

Description

Type

Units

Scaling

Factor

R/W

Range

45796

Conf Prot 2 Param
Select

Unit32

N/A

N/A

RW

0 = Oil Pressure
1 = Coolant Temp
2 = Battery Volts
3 = RPM
4 = Fuel Level
5 = Gen VAB
6 = Gen VBC
7 = Gen VCA
8 = Gen VAN
9 = Gen VBN
10 = Gen VCN
11 = Bus Freq
12 = Bus Volts
13 = Gen Freq
14 = Gen PF
15 = Gen IA
16 = Gen IB
17 = Gen IC
18 = kW A
19 = kW B
20 = kW C
21 = kW Total
22 = kVA A
23 = kVA B
24 = kVA C
25 = kVA Total
26 = Analog Input 1
27 = Analog Input 2
28 = Analog Input 3
29 = Analog Input 4
30 = Analog Input 5
31 = Analog Input 6
32 = Analog Input 7
33 = Analog Input 8
34 = RTD Input 1
35 = RTD Input 2
36 = RTD Input 3
37 = RTD Input 4
38 = RTD Input 5
39 = RTD Input 6
40 = RTD Input 7
41 = RTD Input 8
42 = Thermocouple 1
43 = Thermocouple 2
44 = Fuel Delivery Pressure
45 = kvar A
46 = kvar B
47 = kvar C
48 = kvar Total
49 = Injector Metering Rail Pressure
50 = Total Fuel Used
51 = Fuel Temperature
52 = Engine Oil Temperature
53 = Engine Intercooler Temperature
54 = Coolant Pressure
55 = Fuel Rate
56 = Boost Pressure
57 = Intake Manifold Temperature
58 = Charge Air Temperature
59 = Engine Percent Load
60 = Bus VAB
61 = Bus VBC
62 = Bus VCA
63 = kW Load Percent
64 = Number of Units Online
65 = System kW Capacity
66 = System Total Generated kW
67 = System Total Generated kvar

45798

Conf Prot 2 Hysteresis

Int32

Percent

Deci

RW

0 - 1000

45800

Conf Prot 2 Arming
Delay

Int32

Second

N/A

RW

0 - 300

45802

Conf Prot 2 Threshold 1
Activation Delay

Int32

Second

N/A

RW

0 - 300