INSTALLATION

3-38

HySpeed HSD130 RHF

Instruction Manual

Line disconnect switch

The line disconnect switch serves as the supply-voltage disconnecting (isolating) device. Install
this switch near the power supply for easy access by the operator.

Installation must be performed by a licensed electrician and according to applicable national
and local codes.

The switch should:

isolate the electrical equipment and disconnect all live conductors from the supply
voltage when in the “OFF” position

• have one “OFF” and one “ON” position clearly marked with “O” (OFF) and “l” (ON)

have an external operating handle capable of being locked in the “OFF” position

• contain a power-operated mechanism that serves as an emergency stop
• have slow-blow fuses installed for the proper breaking capacity (see table above).

Power cable

Cable sizes vary based on the distance of the receptacle from the main box. Use a 4-conductor Type SO input power
cable with a conductor temperature rating of 60° C (140° F). Installation must be performed by a licensed electrician.

9

Power requirements

General

All switches, slow-blow fuses and power cables are customer-supplied and must be
chosen as outlined by applicable national and local electrical-codes. Installation must be
performed by a licensed electrician. Use a separate primary-line disconnect switch for
the power supply.

FUSE

SWITCH BOX

Note:

Cable AWG recommendations taken from table 310-16 of the National Electric Code handbook (USA).

Recommended cable size

for 15 m (50 feet)

Input

Rated input current

Recommended

maximum length

voltage

Phase

@ 19.5 kW output

slow-blow fuse size

Rated for 60° C

200/208 VAC

3

62/58 amps

85 amps

30 mm

2

(3 AWG)

220 VAC

3

56 amps

80 amps

30 mm

2

(3 AWG)

240 VAC

3

52 amps

65 amps

26 mm

2

(4 AWG)

400 VAC

3

32 amps

40 amps

10 mm

2

(8 AWG)

440 VAC

3

28 amps

35 amps

8 mm

2

(8 AWG)

480 VAC

3

26 amps

35 amps

8 mm

2

(8 AWG)

600 VAC

3

21 amps

30 amps

6 mm

2

(10 AWG)