SAFETY

03/10

SAFETY

03/10

At some sites, dry dust can represent a potential

explosion hazard.
The U.S. National Fire Protection Association’s 2007

edition of NFPA standard 68, “Explosion Protection by

Deflagration Venting,” provides requirements for the

design, location, installation, maintenance, and use of

devices and systems to vent combustion gases and

pressures after any deflagration event. Consult with

the manufacturer or installer of any dry dust collection

system for applicable requirements before you install

a new dry dust collection system or make significant

changes in the process or materials used with an

existing dry dust collection system.
Consult your local “Authority Having Jurisdiction” (AHJ)

to determine whether any edition of NFPA 68 has been

“adopted by reference” in your local building codes.
Refer to NFPA68 for definitions and explanations of

regulatory terms such as deflagration, AHJ, adopted by

reference, the Kst value, deflagration index, and other

terms.

Note 1 – Hypertherm’s interpretation of these new

requirements is that unless a site-specific evaluation has

been completed to determine that all dust generated is

not combustible, the 2007 edition of NFPA 68 requires

the use of explosion vents designed to the worst-case

Kst value (see annex F) that could be generated from

dust so that the explosion vent size and type can be

designed. NFPA 68 does not specifically identify plasma

cutting or other thermal cutting processes as requiring

deflagration venting systems, but it does apply these

new requirements to all dry dust collection systems.
Note 2 – Users of Hypertherm manuals should consult

and comply with all applicable federal, state, and local

laws and regulations. Hypertherm does not, by the

publication of any Hypertherm manual, intend to urge

action that is not in compliance with all applicable

regulations and standards, and this manual may never

be construed as doing so.

DRY DUST COLLECTION INFORMATION