E2-01: motor rated current – Yaskawa CIMR-PUxA User Manual

Page 106

Advertising
background image

Table 4.26 Constant Output, Settings C to F

Setting = C

90 Hz

Setting = D

120 Hz

Setting = E

180 Hz

Setting = F

60 Hz

0

6

12

200

1.5 3

90

60

V

oltage (V)

Frequency (Hz)

0

6

12

200

1.5 3

120

60

V

oltage (V)

Frequency (Hz)

0

6

12

200

1.5 3

180

60

V

oltage (V)

Frequency (Hz)

0

6.9

230

1.5 3

60

13.8

V

oltage (V)

Frequency (Hz)

Setting a Custom V/f Pattern (Setting F: Default)

Setting parameter E1-03 to F allows the user to set up a custom V/f pattern by changing parameters E1-04 to E1-13.
When initialized, the default values for parameters E1-04 to E1-13 will be equal to Predefined V/f pattern 1.

n

V/f Pattern Settings E1-04 to E1-13

If E1-03 is set to a preset V/f pattern (i.e., a value other than F), the user can monitor the V/f pattern in parameters E1-04

through E1-13. To create a new V/f pattern, set E1-03 to F.

Refer to V/f Pattern on page 106

for an example custom V/f

pattern.

No.

Parameter Name

Setting Range

Default

E1-04

Maximum Output Frequency

40.0 to 400.0 Hz

60.0 Hz

E1-05

Maximum Voltage

0.0 to 255.0 V

<4>

575.0 V

E1-06

Base Frequency

0.0 to [E1-04]

60.0 Hz

E1-07

Middle Output Frequency

0.0 to [E1-04]

3.0 Hz

E1-08

Middle Output Frequency Voltage

0.0 to 255.0 V

<4>

15.0 V

E1-09

Minimum Output Frequency

0.0 to [E1-04]

1.5 Hz

E1-10

Minimum Output Frequency Voltage

0.0 to 255.0 V

<4>

9.0 V

E1-11

Middle Output Frequency 2

0.0 to [E1-04]

0.0 Hz

<6>

E1-12

Middle Output Frequency Voltage 2

0.0 to 255.0 V

<4>

0.0 V

<5>

<6>

E1-13

Base Voltage

0.0 to 255.0 V

<4>

0.0 V

<5>

<7>

<4> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<5> The drive changes these settings when Auto-Tuning is performed (Rotational Auto-Tuning, Stationary Auto-Tuning 1, 2).
<6> Parameter ignored when E1-11 and E1-12 are set to 0.0.
<7> E1-13 and E1-05 are set to the same value when Auto-Tuning is performed.

Output Voltage (V)

Frequency (Hz)

E1-05
E1-12

E1-13

E1-08

E1-10

E1-09

E1-07 E1-06 E1-11 E1-04

Figure 4.18 V/f Pattern

Note:

1. The following condition must be true when setting up the V/f pattern: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
2. To make the V/f pattern a straight line below E1-06, set E1-09 equal to E1-07. In this case the E1-08 setting is disregarded.
3. E1-03 is unaffected when the drive is initialized, but E1-04 through E1-13 return to their default values.
4. Only use E1-11, E1-12, and E1-13 to fine-tune the V/f pattern in the constant output range. These parameters rarely need to be changed.

n

E2-01: Motor Rated Current

Provides motor control, protects the motor, and calculates torque limits. Set E2-01 to the full load amps (FLA) stamped on

the motor nameplate. If Auto-Tuning completes successfully, the value entered to T1-04 will automatically be saved to E2-01.

4.6 Basic Drive Setup Adjustments

106

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide

Advertising