Yaskawa CIMR-PUxA User Manual

Page 203

Advertising
background image

H1 Multi-Function Digital Input Selections

H1-oo

Setting

Function

Description

Page

9

Baseblock command (N.C.)

Open: No drive output

A

Accel/decel ramp hold

Open: Accel/decel is not held

Closed: The drive pauses during acceleration or deceleration and maintains the output

frequency.

B

Drive overheat alarm (oH2)

Closed: Closes when an oH2 alarm occurs

C

Analog terminal input selection

Open: Function assigned by H3-14 is disabled.

Closed: Function assigned by H3-14 is enabled.

F

Through mode

Select this setting when using the terminal in a pass-through mode. The terminal does not

trigger a drive function but can be used as digital input for the controller the drive is connected

to.

10

Up command

The drive accelerates when the Up command terminal closes, and decelerates when the Down

command closes. When both terminals are closed or both are open, the drive holds the

frequency reference. The Up and Down commands must always be used in conjunction with

one another.

11

Down command

The drive accelerates when the Up command terminal closes, and decelerates when the Down

command closes. When both terminals are closed or both are open, the drive holds the

frequency reference. The Up and Down commands must always be used in conjunction with

one another.

12

Forward Jog

Closed: Runs forward at the Jog frequency d1-17.

13

Reverse Jog

Closed: Runs reverse at the Jog frequency d1-17.

14

Fault reset

Closed: Resets faults if the cause is cleared and the Run command is removed.

15

Fast Stop (N.O.)

Closed: Decelerates at the Fast Stop time set to C1-09.

17

Fast Stop (N.C.)

Open: Decelerates to stop at the Fast Stop time set to C1-09.

18

Timer function input

Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction with the

timer function output (H2-oo = 12).

19

PID disable

Open: PID control enabled

Closed: PID control disabled

1A

Accel/decel time selection 2

Used in conjunction with an input terminal set for “Accel/decel time selection 1”

(H1-oo = 7), and allows the drive to switch between accel/decel times 3 and 4.

1B

Program lockout

Open: Parameters cannot be edited (except for U1-01 if the reference source is assigned to

the digital operator).

Closed: Parameters can be edited and saved.

1E

Reference sample hold

Closed: Samples the analog frequency reference and operates the drive at that speed.

20 to 2F External fault

20: N.O., Always detected, ramp to stop

21: N.C., Always detected, ramp to stop

22: N.O., During run, ramp to stop

23: N.C., During run, ramp to stop

24: N.O., Always detected, coast to stop

25: N.C., Always detected, coast to stop

26: N.O., During run, coast to stop

27: N.C., During run, coast to stop

28: N.O., Always detected, Fast Stop

29: N.C., Always detected, Fast Stop

2A: N.O., During run, Fast Stop

2B: N.C., During run, Fast Stop

2C: N.O., Always detected, alarm only (continue running)

2D: N.C., Always detected, alarm only (continue running)

2E: N.O., During run, alarm only (continue running)

2F: N.C., During run, alarm only (continue running)

30

PID integral reset

Closed: Resets the PID control integral value.

31

PID integral hold

Open: Performs integral operation.

Closed: Maintains the current PID control integral value.

32

Multi-Step Speed

Reference 4

Used in combination with input terminals set to Multi-Step Speed Reference 1, 2, and 3. Use

parameters d1-09 to d1-16 to set reference values.

34

PID soft starter cancel

Open: PID soft starter is enabled.

Closed: Disables the PID soft starter b5-17.

35

PID input level selection

Closed: Inverts the PID input signal.

40

Forward run command

(2-Wire sequence)

Open: Stop

Closed: Forward run

Note:

Cannot be set together with settings 42 or 43.

B.6 H Parameters: Multi-Function Terminals

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide

203