Electrical Shock Hazard. Because the leakage current exceeds 3.5 mA in models 4A0414 to 4A1200, IEC/EN

61800-5-1 states that either the power supply must be automatically disconnected in case of discontinuity of the protective earthing

conductor, or a protective earthing conductor with a cross-section of at least 10 mm

2

(Cu) or 16 mm

2

(Al) must be used. Failure to

comply may result in death or serious injury.

C

B

A

A – Braided shield cable

B – Metal panel

C – Cable clamp (conductive)

Figure C.3 Ground Area

6.

Connect a DC link choke to minimize harmonic distortion.

Refer to DC Link Chokes for IEC/EN 61000-3-2

Compliance on page 242

.