Output terminals, Serial communication terminals – Yaskawa CIMR-PUxA User Manual

Page 67

Advertising
background image

n

Output Terminals

Table 3.8

lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function output.

Table 3.8 Control Circuit Output Terminals

Type

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Page

Fault Relay

Output

MA

N.O.

30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A

Minimum load: 5 Vdc, 10 mA

108

MB

N.C. output

MC

Fault output common

Multi-Function
Digital Output

<1>

MD

N.O.

30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A

Minimum load: 5 Vdc, 10 mA

108

ME

N.C. Output

MF

Common (Speed agree)

M1

Multi-function digital output (During run)

30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A

Minimum load: 5 Vdc, 10 mA

M2
M3

Multi-function digital output (Zero speed)

M4

Monitor

Output

FM

Analog monitor output 1 (Output frequency)

-10 to +10 Vdc, or 0 to +10 Vdc

208

AM

Analog monitor output 2 (Output current)

AC

Monitor common

0 V

<1> Refrain from assigning functions to digital relay outputs that involve frequent switching, as doing so may shorten relay performance life. Switching

life is estimated at 200,000 times (assumes 1 A, resistive load).

Connect a suppression diode as shown in

Figure 3.26

when driving a reactive load such as a relay coil. Ensure the diode rating

is greater than the circuit voltage.

A

B

C

D

A – External power, 48 V max.

B – Suppression diode

C – Coil

D – 50 mA or less

Figure 3.26 Connecting a Suppression Diode

n

Serial Communication Terminals

Table 3.9 Control Circuit Terminals: Serial Communications

Type

No.

Signal Name

Function (Signal Level)

MEMOBUS/Modbus
Communication

<1>

R+

Communications input (+)

MEMOBUS/Modbus communication: Use an

RS-422 or RS-485 cable to connect the drive.

RS-422/RS-485

MEMOBUS/Modbus

communication

protocol

115.2 kbps (max.)

R-

Communications input (-)

S+

Communications output (+)

S-

Communications output (-)

IG

Shield ground

0 V

<1> Enable the termination resistor in the last drive in a MEMOBUS/Modbus network by setting DIP switch S2 to the ON position. Refer to the manual

section on Control I/O Connections for more information.

3.7 Control Circuit Wiring

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide