No.

(Addr.

Hex)

Name

Description

Values

Page

F6-64 to

F6-71

(3DF to

3C8)

Reserved

Reserved for Dynamic I/O Assembly Parameters.

F7-01

(3E5)

<2>

IP Address 1

Sets the most significant octet of network static IP address.

Default: 192

Range: 0 to 255

F7-02

(3E6)

<2>

IP Address 2

Sets the second most significant octet of network static IP address.

Default: 168

Range: 0 to 255

F7-03

(3E7)

<2>

IP Address 3

Sets the third most significant octet of network static IP address.

Default: 1

Range: 0 to 255

F7-04

(3E8)

<2>

IP Address 4

Sets the fourth most significant octet of network static IP address.

Default: 20

Range: 0 to 255

F7-05

(3E9)

Subnet Mask 1

Sets the most significant octet of network static Subnet Mask.

Default: 255

Range: 0 to 255

F7-06

(3EA)

Subnet Mask 2

Sets the second most significant octet of network static Subnet Mask.

Default: 255

Range: 0 to 255

F7-07

(3EB)

Subnet Mask 3

Sets the third most significant octet of network static Subnet Mask.

Default: 255

Range: 0 to 255

F7-08

(3EC)

Subnet Mask 4

Sets the fourth most significant octet of network static Subnet Mask.

Default: 0

Range: 0 to 255

F7-09

(3ED)

Gateway Address 1

Sets the most significant octet of network Gateway address.

Default: 192

Range: 0 to 255

F7-10

(3EE)

Gateway Address 2

Sets the second most significant octet of network Gateway address.

Default: 168

Range: 0 to 255

F7-11

(3EF)

Gateway Address 3

Sets the third most significant octet of network Gateway address.

Default: 1

Range: 0 to 255

F7-12

(3E0)

Gateway Address 4

Sets the fourth most significant octet of network Gateway address.

Default: 1

Range: 0 to 255

F7-13

(3F1)

Address Mode at Startup

Select the option address setting method
0: Static

<3>

1: BOOTP

2: DHCP

Default: 2

Range: 0 to 2

F7-14

(3F2)

Duplex Mode Selection

Selects duplex mode setting.

0: Half duplex forced

1: Auto-negotiate duplex mode and communication speed

2: Full duplex forced

Default: 1

Range: 0 to 2

F7-15

(3F3)

Communication Speed

Selection

Sets the communication speed

10: 10 Mbps

100: 100 Mbps

Default: 10

Range: 10, 100

F7-16

(3F4)

Communication Loss

Timeout

Sets the timeout value for communication loss detection in tenths of a second.

A value of 0 disables the connection timeout.

Example: An entered value of 100 represents 10.0 seconds.

Default: 0

Min.: 0

Max.: 300

F7-17

(3F5)

EtherNet/IP Speed Scaling

Factor

Sets the scaling factor for the speed monitor in EtherNet/IP Class ID 2AH

Object.

Default: 0

Min.: -15

Max.: 15

F7-18

(3F6)

EtherNet/IP Current Scaling

Factor

Sets the scaling factor for the output current monitor in EtherNet/IP Class ID

2AH Object.

Default: 0

Min.: -15

Max.: 15

F7-19

(3F7)

EtherNet/IP Torque Scaling

Factor

Sets the scaling factor for the torque monitor in EtherNet/IP Class ID 2AH

Object.

Default: 0

Min.: -15

Max.: 15

F7-20

(3F8)

EtherNet/IP Power Scaling

Factor

Sets the scaling factor for the power monitor in EtherNet/IP Class ID 2AH

Object.

Default: 0

Min.: -15

Max.: 15

F7-21

(3F9)

EtherNet/IP Voltage Scaling

Factor

Sets the scaling factor for the voltage monitor in EtherNet/IP Class ID 2AH

Object.

Default: 0

Min.: -15

Max.: 15

B.5 E: Motor Parameters

200

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide