H3: multi-function analog inputs – Yaskawa CIMR-PUxA User Manual

Page 206

Advertising
background image

H2 Multi-Function Digital Output Settings

H2-oo

Setting

Function

Description

Page

1E

Restart enabled

Closed: An automatic restart is performed

1F

Motor overload alarm (oL1)

Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers this alarm.

20

Drive overheat pre-alarm (oH) Closed: Heatsink temperature exceeds the parameter L8-02 value.

22

Mechanical weakening

detection

Closed: Mechanical weakening detected.

2F

Maintenance period

Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay may require

maintenance.

37

During frequency output

Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial Excitation is

being performed.

Closed: Drive is running the motor (not in a baseblock state and DC Injection is not being

performed).

38

Drive enabled

Closed: Multi-function input set for “Drive enable” is closed (H1-oo = 6A)

39

Watt hour pulse output

Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate the kWh count.

3C

LOCAL/REMOTE status

Open: REMOTE

Closed: LOCAL

3D

During speed search

Closed: Speed Search is being executed.

3E

PID feedback low

Closed: PID feedback level is too low.

3F

PID feedback high

Closed: The PID feedback level is too high.

4A

During KEB Ride-Thru

Closed: KEB Ride-Thru is being performed.

4C

During fast stop

Closed: A Fast Stop command has been entered from the operator or input terminals.

4D

oH Pre-alarm time limit

Closed: oH pre-alarm time limit has passed.

4E

Braking transistor fault (rr)

Closed: The built-in dynamic braking transistor failed.

4F

Braking resistor overheat (oH) Closed: The dynamic braking resistor has overheated.

50

Waiting to Run

Closed: b1-11 Timer is active.

51

Sequence timer 1

Closed: Sequence timer 1 is active.

52

Sequence timer 2

Closed: Sequence timer 2 is active.

53

Sequence timer 3

Closed: Sequence timer 3 is active.

54

Sequence timer 4

Closed: Sequence timer 4 is active.

58

Underload detection

Closed: Underload is detected.

60

Internal cooling fan alarm

Closed: Internal cooling fan alarm

71

Secondary PI Feedback Low

Closed: PI2 feedback level is too low.

72

Secondary PI Feedback High Closed: The PI2 feedback level is too high.

100 to 192 Function 0 to 92 with inverse

output

Inverts the output switching of the multi-function output functions.

Set the last two digits of 1oo to reverse the output signal of that specific function.

u

H3: Multi-Function Analog Inputs

No.

(Addr.

Hex)

Name

Description

Values

Page

H3-01

(410)

Terminal A1 Signal Level

Selection

0: 0 to 10 V

1: -10 to 10 V

2: 4 to 20 mA

3: 0 to 20 mA

Note:

Use Jumper S1 to set input terminal A1 for a current or voltage

input signal.

Default: 0

Range: 0 to 3

110

H3-02

(434)

Terminal A1 Function

Selection

Sets the function of terminal A1.

Default: 0

Range: 0 to 26

110

H3-03

(411)

Terminal A1 Gain Setting

Sets the level of the input value selected in H3-02 when 10 V is input at

terminal A1.

Default: 100.0%

Min.: -999.9

Max.: 999.9

110

H3-04

(412)

Terminal A1 Bias Setting

Sets the level of the input value selected in H3-02 when 0 V is input at terminal

A1.

Default: 0.0%

Min.: -999.9

Max.: 999.9

110

B.6 H Parameters: Multi-Function Terminals

206

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide

Advertising