Protecting main circuit terminals, Table 3.2, Insulation caps or sleeves – Yaskawa CIMR-PUxA User Manual

Page 56: Insulation barrier

Advertising
background image

Table 3.2 Input Fuses for Models 4A0930 and 4A1200

Voltage

Class

Model

Selection

Input Fuse (Example)

Input Voltage

Current

Pre-arc

I

2

t (A

2

s)

Model

Manufacturer

Rating

Pre-arc

I

2

t (A

2

s)

Three-

Phase

400 V

Class

4A0930

480 V

1500 A

140000 to

3100000

CS5F-1200

Fuji Electric

AC500 V, 1200 A

276000

FWH-1200A

Bussman

AC500 V, 1200 A

4A1200

480 V

1500 A

320000 to

3100000

CS5F-1500

Fuji Electric

AC500 V, 1500 A

351000

FWH-1600A

Bussman

AC500 V, 1600 A

u

Protecting Main Circuit Terminals

n

Insulation Caps or Sleeves

Use insulation caps or sleeves when wiring the drive with crimp terminals. Take particular care to ensure that the wiring does

not touch nearby terminals or the surrounding case.

n

Insulation Barrier

Insulation barriers are packaged with drive models 4A0414 through 4A1200 to provide added protection between terminals.

Yaskawa recommends using the provided insulation barriers to ensure proper wiring. Refer to

Figure 3.23

for instructions on

placement of the insulation barriers.

Insulation Barrier

Figure 3.23 Installing Insulation Barriers

3.6 Main Circuit Wiring

56

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide