Yaskawa CIMR-PUxA User Manual

Page 112

Advertising
background image

Parameter H3-08 sets the level of the selected input value that is equal to 0 V input at terminal A3 (bias).

No.

Name

Setting Range

Default

H3-07

Terminal A3 Gain Setting

-999.9 to 999.9%

100.0%

H3-08

Terminal A3 Bias Setting

-999.9 to 999.9%

0.0%

n

H3-09: Terminal A2 Signal Level Selection

Selects the input signal level for analog input A2. Set DIP switch S1 on the terminal board accordingly for a voltage input or

current input.

No.

Name

Setting Range

Default

H3-09

Terminal A2 Signal Level Selection

0 to 3

2

Setting 0: 0 to 10 Vdc

The input level is 0 to 10 Vdc.

Refer to Setting 0: 0 to 10 Vdc on page 110

.

Setting 1: 0 to 10 Vdc Bipolar

The input level is -10 to 10 Vdc.

Refer to Setting 1: 0 to 10 Vdc Bipolar on page 110

.

Setting 2: 4 to 20 mA

The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.

Setting 3: 0 to 20 mA

The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.

n

H3-10: Terminal A2 Function Selection

Determines the function assigned to analog input terminal A2.

No.

Name

Setting Range

Default

H3-10

Terminal A2 Function Selection

0 to 26

0

n

H3-11, H3-12: Terminal A2 Gain and Bias Setting

Parameter H3-11 sets the level of the input value selected that is equal to 10 Vdc input or 20 mA input to terminal A2.
Parameter H3-12 sets the level of the input value selected that is equal to 0 V, 4 mA or 0 mA input at terminal A2.
Use both parameters to adjust the characteristics of the analog input signal to terminal A2. The setting works in the same way

as parameters H3-03 and H3-04 for analog input A1.

No.

Name

Setting Range

Default

H3-11

Terminal A2 Gain Setting

-999.9 to 999.9%

100.0%

H3-12

Terminal A2 Bias Setting

-999.9 to 999.9%

0.0%

n

H4-01, H4-04: Multi-Function Analog Output Terminal FM, AM Monitor Selection

Sets the desired drive monitor parameter Uo-oo to output as an analog value via terminal FM and AM.

Refer to U1:

Operation Status Monitors on page 227

for a list of all monitors. The “Analog Output Level” column indicates whether a

monitor can be used for analog output.
Example: Enter “103” for U1-03.

No.

Name

Setting Range

Default

H4-01

Multi-Function Analog Output Terminal FM Monitor Selection

000 to 999

102

H4-04

Multi-Function Analog Output Terminal AM Monitor Selection

000 to 999

103

A setting of 031 or 000 applies no drive monitor to the analog output. With either of these settings, the output level of the

terminals FM and AM can be set by a PLC via a communication option or MEMOBUS/Modbus (through mode).

4.6 Basic Drive Setup Adjustments

112

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide