background image

No.

(Addr.

Hex)

Name

Description

Values

Page

S2-17

(3216)

Sequence Timer 4 Stop Time

Sets the stop time for timer 4. The value must be set greater than or equal to

S2-16.

Default: 00:00

Min.: 00:00
Max.: 24:00

<1>

S2-18

(3217)

Sequence Timer 4 Day

Selection

Sets the days for which sequence timer 4 is active.

0: Timer disabled

1: Daily

2: Mon - Fri

3: Sat - Sun

4: Monday

5: Tuesday

6: Wednesday

7: Thursday

8: Friday

9: Saturday

10: Sunday

Default: 0

Range: 0 to 10

S2-19

(3218)

Sequence Timer 4 Selection

Sets the action that occurs when sequence timer 4 is active.

0: Digital output only

1: Run

2: Run - PI disable

Default: 0

Range: 0 to 2

S2-20

(3219)

Sequence Timer 4 Reference

Source

Selects the frequency reference source used for running the drive when

sequence timer 4 is active (only applicable when S2-19 is set to 1 or 2).

0: Operator (d1-01)

1: Operator (d1-02)

2: Operator (d1-03)

3: Operator (d1-04)

4: Terminals

5: Serial communication

6: Option card

7: Pulse input

Default: 0

Range: 0 to 7

<1> Setting the sequence timer start time to a higher value than the sequence timer stop time disables that sequence timer.

u

S3: Secondary PI (PI2) Control

No.

(Addr.

Hex)

Name

Description

Values

Page

S3-01

(321A)

Secondary PI Enable

Selection

Determines when the secondary PI controller is enabled.

0: Disabled

1: Always

2: Drive running

3: Motor running

Note:

Setting 3 does not run the motor at zero speed, baseblock, or in

DC injection.

Default: 0

Range: 0 to 3

S3-02

(321B)

Secondary PI User Display

Sets the scale value of 100% PI input.

Default: 10000

Min.: 0

Max.: 60000

S3-03

(321C)

Secondary PI Display Digits

Sets the decimal place display for secondary PI units.

0: No decimal places

1: One decimal place

2: Two decimal places

3: Three decimal places

Default: 2

Range: 0 to 3