Parameter b5-91, EZ Minimum Speed, acts as a lower limit on the PID output. This value is internally limited to the higher

value between b5-34 or d2-02 and is active regardless of the b5-89 setting. When this limit is active, the PID integrator will

be held to avoid integral wind-up. Parameter b5-90 determines whether the value is input in Hz or RPM.
Sleep
When the output frequency (or speed) is at or below the EZ Sleep Level (b5-92) for the time set in EZ Sleep Time (b5-93),

the drive will sleep. The EZ Sleep Level is internally lower limited to the b5-92 setting.
Wake-up using Absolute Level (b5-95 = 0)
For Normal Acting PID, the PID Feedback must drop below the EZ Wake-up Level (b5-94) for the time set in EZ Wake-up

Time (b5-96) in order for the drive to wake-up.
For Reverse Acting PID, the PID Feedback must rise above the b5-94 level for the time set in b5-96 in order for the drive to

wake-up.
Wake-up using Setpoint Delta Level (b5-95 = 1)
For Normal Acting PID, the wake-up level is determined by the PID Setpoint minus the b5-94 level. The PID Feedback must

drop below the wake-up level for the time set in b5-96 in order for the drive to wake-up
For Reverse Acting PID, the wake-up level is determined by the PID Setpoint plus the b5-94 level. The PID Feedback must

rise above the wake-up level for the time set in b5-96 in order for the drive to wake-up.
Refer to

Figure 4.14

and

Figure 4.15

for detailed diagrams of EZ Sleep/Wake-up functions.

Refer to

Table 4.10

for descriptions of EZ Sleep/Wake-up parameters.

PID Set-point

Run Command

Output Frequency

Wake-up Level <1>

b5 -96

Minimum Speed

(b5-91) <2>

b5 -93

b5 -93

Wake-up

Level

reached

Wake-up

Timer

expired

Sleep

Level

reached

Sleep

Level

reached

Sleep
Timer

expired

Above

Sleep

Level

b5-9 6

b5-9 6

b5-96

Wake-up

Level

reached

Wake-up

Timer

expired

Wake-up

Level

reached

Wake-up

Level

reached

Above

Wake-up

Level

Above

Wake-up

Level

<1> Determined by EZ Wake-up Level (b5-94) and EZ Wake-up Mode (b5-95)

<2> EZ Sleep Level (b 5-92) is left at default (0.0 Hz), thus effectively making b 5-91 the Sleep Level

PID Feedback

Sleeping

Sleeping

Figure 4.14 EZ Sleep/Wake-up with Normal Acting PID and b5-92 = 0.0 Hz