B.11 T: Motor Tuning

Enter data into the following parameters to tune the motor and drive for optimal performance.

u

T1: Induction Motor Auto-Tuning

No.

(Addr.

Hex)

Name

Description

Values

Page

T1-01

(701)

Auto-Tuning Mode

Selection

2: Stationary Auto-Tuning for Line-to-Line Resistance

3: Rotational Auto-Tuning for V/f Control (necessary for Energy Savings and

Speed Estimation Speed Search)

Default: 2

Range: 2, 3

T1-02

(702)

Motor Rated Power

Sets the motor rated power as specified on the motor nameplate.

Note:

Use the following formula to convert horsepower into kilowatts:

1HP = 0.746 kW.

Default:

<1>

Min.: 0.00 kW

Max.: 650.00 kW

T1-03

(703)

Motor Rated Voltage

Sets the motor rated voltage as specified on the motor nameplate.

Default: 200.0 V

<2>

Min: 0.0
Max: 255.0

<2>

T1-04

(704)

Motor Rated Current

Sets the motor rated current as specified on the motor nameplate.

Default:

<1>

Min.: 10% of drive

rated current

Max.: 200% of

drive rated current

T1-05

(705)

Motor Base Frequency

Sets the rated frequency of the motor as specified on the motor nameplate.

Default: 60.0 Hz

Min.: 0.0

Max.: 400.0

T1-06

(706)

Number of Motor Poles

Sets the number of motor poles as specified on the motor nameplate.

Default: 4

Min.: 2

Max.: 48

T1-07

(707)

Motor Base Speed

Sets the rated speed of the motor as specified on the motor nameplate.

Default: 1750 r/min

Min.: 0

Max.: 24000

T1-11

(70B)

Motor Iron Loss

Sets the iron loss for determining the Energy Saving coefficient.

The value is set to E2-10 (motor iron loss) set when the power is cycled. If

T1-02 is changed, a default value appropriate for the motor capacity that was

entered will appear.

Default: 14 W

<3>

Min.: 0

Max.: 65535

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<3> Default setting value differs depending on the motor code value and motor parameter settings.

B.11 T: Motor Tuning

226