F6, f7: communication option card – Yaskawa CIMR-PUxA User Manual

Page 198

Advertising
background image

No.

(Addr.

Hex)

Name

Description

Values

Page

F4-08

(398)

Terminal V2 Signal Level

0: 0 to 10 V

1: -10 to 10 V

Default: 0

Range: 0, 1

u

F6, F7: Communication Option Card

Parameters F6-01 through F6-03 and F6-06 through F6-08 are used for CC-Link, CANopen, DeviceNet, PROFIBUS-DP, and

MECHATROLINK-II options. Other parameters in the F6 group are used for communication-protocol-specific settings. F7

parameters are used for EtherNet/IP, Modbus TCP/IP, and PROFINET options.

No.

(Addr.

Hex)

Name

Description

Values

Page

F6-01

(3A2)

Communications Error

Operation Selection

0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.

1: Coast to stop.

2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.

3: Alarm only.

Default: 1

Range: 0 to 3

F6-02

(3A3)

External Fault from Comm.

Option Detection Selection

0: Always detected.

1: Detection during run only.

Default: 0

Range: 0, 1

F6-03

(3A4)

External Fault from Comm.

Option Operation Selection

0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.

1: Coast to stop.

2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.

3: Alarm only.

Default: 1

Range: 0 to 3

F6-04

(3A5)

bUS Error Detection Time

Sets the delay time for error detection if a bus error occurs.

Default: 2.0 s

Min.: 0.0

Max.: 5.0

F6-07

(3A8)

Multi-Step Speed Enable/

Disable Selection when

NefRef/ComRef is Selected

0: Multi-step reference disabled (same as F7)

1: Multi-step reference enabled (same as V7)

Default: 0

Range: 0, 1

F6-08

(36A)

<1>

Reset Communication

Parameters

0: Communication-related parameters (F6-oo) are not reset when the drive

is initialized using A1-03.

1: Reset all communication-related parameters (F6-oo) when the drive is

initialized using A1-03.

Default: 0

Range: 0, 1

F6-10

(3B6)

CC-Link Node Address

Sets the node address if a CC-Link option is installed.

Default: 0

Min.: 0

Max.: 64

F6-11

(3B7)

CC-Link Communication

Speed

0: 156 Kbps

1: 625 Kbps

2: 2.5 Mbps

3: 5 Mbps

4: 10 Mbps

Default: 0

Range: 0 to 4

F6-14

(3BB)

CC-Link bUS Error Auto

Reset

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

F6-20

(36B)

MECHATROLINK Station

Address

Sets the station address when the MECHATROLINK-II option has been

installed.

Default: 21

Min.: 20

Max.: 3F

F6-21

(36C)

MECHATROLINK Frame

Size

0: 32 byte

1: 17 byte

Default: 0

Range: 0, 1

F6-22

(36D)

MECHATROLINK Link

Speed

0: 10 Mbps

1: 4 Mbps

Default: 0

Range: 0, 1

F6-23

(36E)

MECHATROLINK

Monitor Selection (E)

Sets the MECHATROLINK-II monitor (E).

Default: 0

Min.: 0

Max.: FFFF

F6-24

(36F)

MECHATROLINK

Monitor Selection (F)

Sets the MECHATROLINK-II monitor (F).

Default: 0

Min.: 0

Max.: FFFF

F6-25

(3C9)

Operation Selection at

Watchdog Timer Error (E5)

0: Ramp to stop. Decelerate using the deceleration time in C1-02.

1: Coast to stop

2: Fast stop. Decelerate using the deceleration time in C1-09.

3: Alarm only

Default: 1

Range: 0 to 3

F6-26

(3CA)

MECHATROLINK bUS

Errors Detected

Sets the number of option communication errors (bUS).

Default: 2

Min.: 2

Max.: 10

B.5 E: Motor Parameters

198

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide