Default values for fan and pump applications – Yaskawa CIMR-PUxA User Manual

Page 127

Advertising
background image

u

Default Values for Fan and Pump Applications

Table 4.35 Fan and Pump Application Defaults

A1-03 Setting

Parameter

8008

8009

8010

8011

A1-02

0: V/f Control

0: V/f Control

0: V/f Control

0: V/f Control

b1-04

–

–

1: Reverse Disabled

1: Reverse Disabled

b3-05

–

–

10.0 s

10.0 s

b5-01

–

1: PID Enabled

–

1: PID Enabled

b5-03

–

–

–

5.0 s

b5-08

–

–

–

2.00 s

b5-13

–

–

–

2%

b5-14

–

–

–

25.0 s

b5-18

–

1: Enabled (b5-19)

–

1: Enabled (b5-19)

b5-20

–

3: User Set

–

3: User Set

b5-46

–

–

–

1: PSI

b5-89

–

1: EZ Sleep/Wake Up

–

1: EZ Sleep/Wake Up

C1-01

–

–

90.0 s

60.0 s

C1-02

–

–

90.0 s

60.0 s

C2-01

–

–

5.00 s

5.00 s

C2-02

–

–

5.00 s

5.00 s

C2-03

–

–

5.00 s

5.00 s

C2-04

–

–

5.00 s

5.00 s

H3-10

–

B: PID Feedback

B: PID Feedback

L2-01

2: CPU Active

2: CPU Active

2: CPU Active

2: CPU Active

L3-02

–

–

110%

110%

L3-06

–

–

100%

100%

L4-05

–

–

0: Stop

–

L5-04

–

–

180.0 s

180.0 s

L5-05

1: L5-04 Interval

1: L5-04 Interval

1: L5-04 Interval

1: L5-04 Interval

o1-06

–

1: Selectable

–

1: Selectable

o1-07

–

102: Output Frequency

–

102: Output Frequency

o1-08

–

501: Feedback

–

501: Feedback

4.11 Fan and Pump Application Presets

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide

127

4

Start-Up Programming & Operation

Advertising