S3-04

(321D)

Secondary PI Unit

Selection

Sets the units for the secondary PI control function.

0: Inch of water (WC)

1: Pounds per square inch (PSI)

2: Gallons per minute (GPM)

3: Degrees Fahrenheit (F)

4: Cubic feet per minute (CFM)

5: Cubic meters per hour (CMH)

6: Liters per hour (LPH)

7: Liters per second (LPS)

8: Bar (Bar)

9: Pascals (Pa)

10: Degrees Celsius (C)

11: Meters (Mtr) (Ft: Feet)

12: Liters per minute (LPM)

13: Cubic meters per minute (CMM)

14: No unit

15: Percentage (%)

Default: 15

Range: 0 to 15

S3-05

(321E)

Secondary PI Setpoint Value

Sets the secondary PI controller target value.

Default: 0.00

<1>

Min.: 0.00
Max.: 600.00

<2>

S3-06

(321F)

Secondary PI Proportional

Gain Setting

Sets the proportional gain of the secondary PI controller. A setting of 0.00

disables P control.

Default: 1.00

Min.: 0.00

Max.: 25.00

S3-07

(3220)

Secondary PI Integral Time

Setting

Sets the integral time for the secondary PI controller. A setting of 0.0 s disables

integral control.

Default: 1.0 s

Min.: 0.0

Max.: 360.0

S3-08

(3221)

Secondary PI Integral Limit

Setting

Sets the maximum output possible from the integrator.

Default: 100.0%

Min.: 0.0

Max.: 100.0

S3-09

(3222)

Secondary PI Output Upper

Limit

Sets the maximum output possible from the secondary PI controller.

Default: 100.0%

Min.: 0.0

Max.: 100.0

S3-10

(3223)

Secondary PI Output Lower

Limit

Sets the minimum output possible from the secondary PI controller.

Default: 0.00%

Min.: -100.00

Max.: 100.00

S3-11

(3224)

Secondary PI Output Level

Selection

Sets the secondary PI controller output direction.

0: Normal Output (direct acting)

1: Reverse Output (reverse acting)

Default: 0

Range: 0, 1

S3-12

(3225)

Secondary PI Disable Mode

Selects the secondary PI controller output when disabled.

0: No output (0%)

1: Lower Limit (S3-10)

2: Setpoint

Default: 0

Range: 0 to 2

S3-13

(3226)

Secondary PI Low Feedback

Detection Level

Sets the secondary PI low feedback detection level.

Default: 0.00

<1>

Min.: 0.00
Max.: 600.00

<2>

S3-14

(3227)

Secondary PI Low Feedback

Detection Time

Sets the secondary PI low feedback detection delay time in seconds.

Default: 1.0 s

Min.: 0.0

Max.: 25.5

S3-15

(3228)

Secondary PI High

Feedback Level

Sets the secondary PI high feedback detection level.

Default: 100.00

<1>

Min.: 0.00
Max.: 600.00

<2>

S3-16

(3229)

Secondary PI High

Feedback Detection Time

Sets the secondary PI high feedback detection delay time in seconds.

Default: 1.0 s

Min.: 0.0

Max.: 25.5

S3-17

(322A)

Secondary PI Feedback

Detection Selection

Selects when secondary PI controller low and high feedback detection are

active.

0: Secondary PI enabled

1: Always

Default: 0

Range: 0, 1

<1> Unit is determined by S3-04.
<2> Upper limit is S3-02, decimal placeholder is determined by S3-03.

B.10 S: Special Application

224