Yaskawa CIMR-PUxA User Manual

Page 138

Advertising
background image

The rated current of the motor being used is

less than 5% of the drive rated current

Check the drive and motor capacities.

An output transistor is damaged

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

A single-phase motor is being used

The drive cannot operate a single phase motor.

Digital Operator Display

Fault Name

<1>

LF3

Power Unit Output Phase Loss 3
• Phase loss occurred on the output side
• Setting L8-78 to 1 enables Power Unit Output Phase Loss Protection

Cause

Possible Solution

The gate drive board in the power unit is

damaged.

Cycle the power supply. If the fault continues to occur, replace the gate drive board or the drive. Contact

Yaskawa or a Yaskawa representative for instructions on replacing the gate drive board.

Cable to the current detection circuit in the

power unit is damaged or not connected

properly.

Check for incorrect wiring and correct any wiring mistakes.

Cable between the output rector and the power

unit is loose or not connected.

Contact Yaskawa or your nearest sales representative for instructions.

<1> Detected in models 4A0930 and 4A1200.

Digital Operator Display

Fault Name

nSE

Node Setup Error
A terminal assigned to the node setup function closed during run.

Cause

Possible Solution

The node setup terminal closed during run.

Stop the drive when using the node setup function.

A Run command was issued while the node

setup function was active.

Digital Operator Display

Fault Name

oC

Overcurrent
Drive sensors detected an output current greater than the specified overcurrent level.

Cause

Possible Solution

The motor has been damaged due to

overheating or the motor insulation is

damaged

• Check the insulation resistance.
• Replace the motor.

One of the motor cables has shorted out or

there is a grounding problem

• Check the motor cables.
• Remove the short circuit and reapply power to the drive.
• Check the resistance between the motor cables and the ground terminal .
• Replace damaged cables.

The load is too heavy

• Measure the current flowing into the motor.
• Replace the drive with a larger capacity drive if the current value exceeds the rated current.
• Determine if there is sudden fluctuation in the current level.
• Reduce the load to avoid sudden changes in the current level or switch to a larger drive.

The acceleration or deceleration times are too

short

Calculate the torque needed during acceleration relative to the load inertia and the specified acceleration

time. If it is not possible to set the proper amount of torque, make the following changes:
• Increase the acceleration time (C1-01, C1-03).
• Increase the S-curve characteristics (C2-01 through C2-04).
• Increase the capacity of the drive.

The drive is attempting to operate a specialized

motor or a motor larger than the maximum size

allowed

• Check the motor capacity.
• Ensure that the rated capacity of the drive is greater than or equal to the capacity rating found on the

motor nameplate.

Magnetic contactor (MC) on the output side of

the drive has turned on or off

Set up the operation sequence so the MC does not trip while the drive is outputting current.

V/f setting is not operating as expected

• Check the ratios between the voltage and frequency.
• Set parameters E1-04 through E1-10 appropriately.
• Lower the voltage if it is too high relative to the frequency.

Excessive torque compensation

• Check the amount of torque compensation.
• Reduce the torque compensation gain (C4-01) until there is no speed loss and less current.

5.2 Fault Detection

138

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide

Advertising