3.6 Main Circuit Wiring

This section describes the functions, specifications, and procedures required to safely and properly wire the main circuit in

the drive.

NOTICE:

Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen over time. Improper wiring practices

could result in drive malfunction due to loose terminal connections.
NOTICE:

Do not switch the drive input to start or stop the motor. Frequently switching the drive on and off shortens the life of the DC bus

charge circuit and the DC bus capacitors, and can cause premature drive failures. For the full performance life, refrain from switching the

drive on and off more than once every 30 minutes.

Refer to Input Fuse Installation on page 248

for details on fuse selection.

u

Main Circuit Terminal Functions

Table 3.1 Main Circuit Terminal Functions

Terminal

Type

Function

Page

200 V

Class

Drive Model

2A0004 to

2A0081

2A0110, 2A0138

2A0169 to

2A0415

400 V

Class

4A0002 to

4A0044

4A0058, 4A0072

4A0088 to

4A0675

4A0930, 4A1200

600 V

Class

5A0003 to

5A0032

5A0041, 5A0052

5A0062 to

5A0242

R/L1

Main circuit power supply input

Connects line power to the drive

43

S/L2

T/L3

R1-L11

Not available

Main circuit power

supply input

Connects line power to the drive

Remove the shorting bars

connecting R/L1-R1/L11, S/L2-

S1/L21, T/L3-T1/L31 when

using 12-phase rectification.

S1-L21

T1-L31

U/T1

Drive output

Connects to the motor

43

V/T2

W/T3

B1

Braking resistor

Not available

Available for connecting a

braking resistor or a braking

resistor unit option

B2

2

• DC link choke

connection

(

⊕1, ⊕2)

(remove the

shorting bar

between

⊕1 and ⊕2)

• DC power

supply input

(

⊕1, ⊖)

Not available

For connecting:
• the drive to a DC power supply
• dynamic braking options
• a DC link choke

1

DC power supply

input

(

⊕1, ⊖)

• DC power supply input (

⊕1, ⊖)

• Braking unit connection (

⊕3, ⊖)

3

Not available

For 200 V class: 100 Ω or less

For 400 V class: 10 Ω or less

For 600 V class: 10 Ω or less

Grounding terminal

64

Note:

Use terminals B1 and

⊖ when installing a CDBR-type braking unit on drives with built-in braking transistors (Models 2A0004 to 2A0138,

4A0002 to 4A0072, and 5A0003 to 5A0052).

Wiring Fuses for Models 4A0930 and 4A1200

NOTICE:

If a fuse is blown or an Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of peripheral devices

to identify the cause. Contact Yaskawa before restarting the drive or the peripheral devices if the cause cannot be identified.

Install a fuse on the input side to protect drive wiring and prevent other secondary damage. Wire the fuse so that leakage

current in the upper controller power supply will trigger the fuse and shut off the power supply.
Select the appropriate fuse from

Table 3.2

.

3.6 Main Circuit Wiring

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide

55

3

Electrical Installation

Advertising