Terminal am/fm signal selection, 8 control i/o connections – Yaskawa CIMR-PUxA User Manual

Page 73

Advertising
background image

V

I

A1 A2 A3

Jumper S1

Figure 3.34 Terminal A2 Set to Current Input; A1 and A3 Set to Voltage Input

Table 3.13 Jumper S1 Settings

Setting

Description

V (top position)

Voltage input (-10 to +10 V or 0 to 10 V)

I (bottom position)

Current input (4 to 20 mA or 0 to 20 mA)

Table 3.14 Voltage/Current Selection Parameter Details

No.

Parameter Name

Description

Setting

Range

Default

Setting

H3-01

Terminal A1 signal level selection

Selects the signal level for terminal A1.

0: 0 to 10 Vdc

1: 0 to 10 Vdc Bipolar

2: 4 to 20 mA

3: 0 to 20 mA

0 to 3

0

H3-05

Terminal A3 signal level selection

Selects the signal level for terminal A3.

0: 0 to 10 Vdc

1: 0 to 10 Vdc Bipolar

2: 4 to 20 mA

3: 0 to 20 mA

0 to 3

0

H3-09

Terminal A2 signal level selection

Selects the signal level for terminal A2.

0: 0 to 10 Vdc

1: 0 to 10 Vdc Bipolar

2: 4 to 20 mA

3: 0 to 20 mA

0 to 3

2

u

Terminal AM/FM Signal Selection

The signal type for terminals AM and FM can be set to either voltage or current output using jumper S5 on the terminal board

as explained in

Table 3.15

. When changing the setting of jumper S5, parameters H4-07 and H4-08 must be set accordingly.

The default selection is voltage output for both terminals.

Table 3.15 Jumper S5 Settings

Terminal

Voltage Output

Current Output

Terminal AM

AM

FM

V

I

AM

FM

V

I

Terminal FM

AM

FM

V

I

AM

FM

V

I

Table 3.16 Parameter H4-07 and H4-08 Details

No.

Parameter Name

Description

Setting

Range

Default

Setting

H4-07

Terminal AM signal level selection

0: 0 to 10 Vdc

1: -10 to 10 Vdc

2: 4 to 20 mA

0 to 2

0

H4-08

Terminal FM signal level selection

3.8 Control I/O Connections

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide