Setup Group Parameters

Table 4.6

lists the parameters available by default in the Setup Group. Selecting an Application Preset in through initialization

in parameter A1-03 automatically changes the parameters selected for the Setup Group.

Refer to Fan and Pump Application

Presets on page 125

for details on parameters and default values for the fan and pump Setup Groups.

No.

Parameter Name

Setting Range

Default

A1-03

Initialize Parameters

0, 1110, 2220, 3330, 5550,

8008, 8009, 8010, 8011

0

Setting 0: No initialization (default)
Setting 1110: User Initialize (parameter values must be stored using parameter o2-03)
Setting 2220: 2-Wire Initialize
Setting 3330: 3-Wire Initialize
Setting 5550: Terminal/Control Initialize
Setting 8008: Pump
Setting 8009: Pump w/ PI
Setting 8010: Fan
Setting 8011: Fan w/ PI
Use the Programming Mode to access parameters not displayed in the Setup Group.

Table 4.6 General Purpose Application Setup Group Parameters (A1-03 = 0)

Parameter

Name

A1-06

Application Preset Selection (Monitor only)

b1-01

Frequency Reference Selection 1

b1-02

Run Command Selection 1

b1-03

Stopping Method Selection

b1-04

Reverse Operation Selection

C1-01

Acceleration Time 1

C1-02

Deceleration Time 1

d1-01

Frequency Reference 1

d2-01

Frequency Reference Upper Limit

d2-02

Frequency Reference Lower Limit

Parameter

Name

E2-01

Motor Rated Current

L2-01

Momentary Power Loss Operation Selection

L5-01

Number of Auto Restart Attempts

L6-01

Torque Detection 1 Selection

L6-02

Torque Detection 1 Level

L6-03

Torque Detection 1 Time

o1-06

User Monitor Selection Mode

o1-07

Second Line Monitor Selection

o1-08

Third Line Monitor Selection

u

Switching Between LOCAL and REMOTE

LOCAL mode is when the drive is set to accept the Run command from the digital operator RUN key. REMOTE mode is

when the drive is set to accept the Run command from an external device (i.e., input terminals or serial communications).

WARNING!

Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from

LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Be sure all personnel are clear of rotating machinery.

Switch the operation between LOCAL and REMOTE using the LO/RE key on the digital operator or via a digital input.

Note:

1. After selecting LOCAL, the LO/RE light will remain lit.
2. The drive will not allow the user to switch between LOCAL and REMOTE during run.

4.2 The Drive, Programming, and Clock Adjustment Modes

86