Low Voltage Wiring for Control Circuit Terminals

Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. The external

power supply shall be a UL listed Class 2 power supply source or equivalent only.

Table C.6 Control Circuit Terminal Power Supply

Input / Output

Terminal Signal

Power Supply Specifications

Digital inputs

S1 to S8, SC

Use the internal LVLC power supply of the drive. Use class

2 for external power supply.

Analog inputs / outputs

+V, A1, A2, A3, AC, AM, FM

Use the internal LVLC power supply of the drive. Use class

2 for external power supply.

n

Drive Short Circuit Rating

The drive is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240 Vac

maximum (200 V Class), 480 Vac maximum (400 V Class), and 600 Vac maximum (600 V Class) when protected by Bussmann

Type FWH or FWP fuses as specified in

Factory Recommended Branch Circuit Protection

on page

236

.

u

CSA Standards Compliance

Figure C.7 CSA Mark

n

CSA for Industrial Control Equipment

The drive is CSA-certified as Industrial Control Equipment Class 3211.
Specifically, the drive is certified to: CAN/CSA C22.2 No. 04-04 and CAN/CSA C22.2 No.14-05.

u

Drive Motor Overload Protection

Set parameter E2-01 (motor rated current) to the appropriate value to enable motor overload protection. The internal motor

overload protection is UL listed and in accordance with the NEC and CEC.

n

E2-01: Motor Rated Current

Setting Range: Model-dependent
Default Setting: Model-dependent
Parameter E2-01 protects the motor when parameter L1-01 is not set to 0. The default for L1-01 is 1, which enables protection

for standard induction motors.
If Auto-Tuning has been performed successfully, the motor data entered to T1-04 is automatically written to parameter E2-01.

If Auto-Tuning has not been performed, manually enter the correct motor rated current to parameter E2-01.

C.2 UL and CSA Standards

250

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide