Yaskawa CIMR-PUxA User Manual

Page 232

Advertising
background image

No.

(Addr.

Hex)

Name

Description

Analog Output Level

Unit

U4-13

(7CF)

Peak Hold Current

Displays the highest current value that occurred during run.

No signal output

available

0.01 A

<1>

U4-14

(7D0)

Peak Hold Output

Frequency

Displays the output frequency when the current value shown in U4-13

occurred.

No signal output

available

0.01 Hz

U4-16

(7D8)

Motor Overload Estimate

(oL1)

Shows the value of the motor overload detection accumulator. 100% is

equal to the oL1 detection level.

10 V: 100%

0.1%

U4-18

(7DA)

Frequency Reference

Source Selection

Displays the source for the frequency reference as XY-nn.

X: indicates which reference is used:

1 = Reference 1 (b1-01)

2 = Reference 2 (b1-15)

Y-nn: indicates the reference source

0-01 = Digital operator

1-01 = Analog (terminal A1)

1-02 = Analog (terminal A2)

1-03 = Analog (terminal A3)

2-02 to 17 = Multi-step speed (d1-02 to 17)

3-01 = MEMOBUS/Modbus communications

4-01 = Communication option card

5-01 = Pulse input

No signal output

available

U4-19

(7DB)

Frequency Reference from

MEMOBUS/Modbus

Comm.

Displays the frequency reference provided by MEMOBUS/Modbus

(decimal).

No signal output

available

0.01%

U4-20

(7DC)

Option Frequency

Reference

Displays the frequency reference input by an option card (decimal).

No signal output

available

U4-21

(7DD)

Run Command Source

Selection

Displays the source for the Run command as XY-nn.

X: Indicates which Run source is used:

1 = Reference 1 (b1-02)

2 = Reference 2 (b1-16)

Y: Input power supply data

0 = Digital operator

1 = External terminals

3 = MEMOBUS/Modbus communications

4 = Communication option card

nn: Run command limit status data

00: No limit status.

01: Run command was left on when stopped in the PRG mode

02: Run command was left on when switching from LOCAL to REMOTE

operation

03: Waiting for soft charge bypass contactor after power up (Uv or Uv1

flashes after 10 s)

04: Waiting for “Run command prohibited” time period to end

05: Fast Stop (digital input, digital operator)

06: b1-17 (Run command given at power-up)

07: During baseblock while coast to stop with timer

08: Frequency reference is below minimal reference during baseblock

09: Waiting for Enter command

No signal output

available

U4-22

(7DE)

MEMOBUS/Modbus

Communications

Reference

Displays the drive control data set by MEMOBUS/Modbus

communications register no. 0001H as a four-digit hexadecimal number. No signal output

available

U4-23

(7DF)

Communication Option

Card Reference

Displays drive control data set by an option card as a four-digit hexadecimal

number.

No signal output

available

U4-32

(7FB)

Motor Temperature (NTC)

Displays the motor temperature (NTC).

U4-32 will display “20 °C” when a multi-function analog input is not set

for motor thermistor input (H1-oo = 17H).

200 °C

1 °C

U4-37

(1044)

oH Alarm Location

Monitor

Displays the module where the oH alarm occurred as a binary number.

No signal output

available

U4-38

(1045)

FAn Alarm Location

Monitor

Displays the module where the FAn alarm occurred as a binary number.

No signal output

available

U4-39

(1046)

voF Alarm Location

Monitor

Displays the module where the voF alarm occurred as a binary number.

No signal output

available

<1> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.

B.12 U: Monitors

232

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide