Yaskawa CIMR-PUxA User Manual

Page 188

Advertising
background image

No.

(Addr.

Hex)

Name

Description

Values

Page

b5-14

(1B2)

PID Feedback Loss

Detection Time

Sets a delay time for PID feedback loss.

Default: 1.0 s

Min.: 0.0

Max.: 25.5

b5-15

(1B3)

PID Sleep Function Start

Level

Sets the frequency level that triggers the sleep function.

Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

b5-16

(1B4)

PID Sleep Delay Time

Sets a delay time before the sleep function is triggered.

Default: 0.0 s

Min.: 0.0

Max.: 25.5

b5-17

(1B5)

PID Accel/Decel Time

Sets the acceleration and deceleration time to PID setpoint.

Default: 0.0 s

Min.: 0.0

Max.: 6000.0

b5-18

(1DC)

PID Setpoint Selection

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

b5-19

(1DD)

<1>

PID Setpoint Value

Sets the PID target value as a percentage of the maximum output frequency

when b5-18 is set to 1.

Note:

Values set above b5-38 will be internally limited to b5-38

Default: 0.00%

Min.: 0.00

Max.: 600.00

b5-20

(1E2)

PID Setpoint Scaling

0: 0.01 Hz units

1: 0.01% units (100% = max output frequency)

2: RPM (number of motor poles must entered)

3: User-set (set scaling to b5-38 and b5-39, units based on b5-46 setting)

Default: 1

Range: 0 to 3

b5-34

(19F)

PID Output Lower Limit

Sets the minimum output possible from the PID controller as a percentage of

the maximum output frequency.

Default: 0.00%

Min.: -100.00

Max.: 100.00

b5-35

(1A0)

PID Input Limit

Limits the PID control input (deviation signal) as a percentage of the maximum

output frequency. Acts as a bipolar limit.

Default: 1000.0%

Min.: 0.0

Max.: 1000.0

b5-36

(1A1)

PID Feedback High

Detection Level

Sets the PID feedback high detection level as a percentage of the maximum

output frequency.

Default: 100%

Min.: 0

Max.: 100

b5-37

(1A2)

PID Feedback High

Detection Time

Sets the PID feedback high level detection delay time.

Default: 1.0 s

Min.: 0.0

Max.: 25.5

b5-38

(1FE)

PID Setpoint User Display

Scales the PID units to the maximum output frequency.

Default: 10000

Min.: 1

Max.: 60000

b5-39

(1FF)

PID Setpoint Display Digits

0: No decimal places

1: One decimal place

2: Two decimal places

3: Three decimal places

Default: 2

Range: 0 to 3

b5-40

(17F)

Frequency Reference

Monitor Content during PID

0: Display the frequency reference (U1-01) after PID compensation has been

added.

1: Display the frequency reference (U1-01) before PID compensation has been

added.

Default: 0

Range: 0, 1

b5-41

(160)

PI Output 2 Unit Selection

0: WC (Inch of water)

1: PSI (Pounds per square inch)

2: GPM (Gallons per minute)

3: F (Degrees Fahrenheit)

4: CFM (Cubic feet per minute)

5: CMH (Cubic meters per hour)

6: LPH (Liters per hour)

7: LPS (Liters per second)

8: Bar (Bar)

9: Pa (Pascal)

10: C (Degrees Celsius)

11: Mtr (Meters)

12: Ft (Feet)

13: LPM (Liters per minute)

14: CMM (Cubic meters per minute)

15: “Hg (Inches of Mercury)

25: None

Default: 0

Range: 0 to 15; 25

B.2 b: Application

188

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide