Yaskawa CIMR-PUxA User Manual

Page 189

Advertising
background image

No.

(Addr.

Hex)

Name

Description

Values

Page

b5-42

(161)

PI Output 2 Calculation

Mode

0: Linear - the monitor displays PID output

1: Square root - the monitor displays square root PID output

2: Quadratic - the monitor displays 1/(PID output)

3: Cubic - the monitor displays 1/(PID output)

Note:

Used for U5-14 and U5-15 only.

Default: 0

Range: 0 to 3

b5-43

(162)

PI Output 2 Monitor Max

Upper 4 Digits

Sets the upper 4 digits of the maximum monitor value.

Used with b5-44 to set maximum monitor value of U5-14 and U5-15 at

maximum frequency.

Note:

Used for U5-14 and U5-15 only.

Default: 0

Min.: 0

Max.: 9999

b5-44

(163)

PI Output 2 Monitor Max

Lower 4 Digits

Sets the lower 4 digits of the maximum monitor value.

Used with b5-43 to set maximum monitor value of U5-14 and U5-15 at

maximum frequency.

Note:

Used for U5-14 and U5-15 only.

Default: 0

Min.: 0

Max.: 99.99

b5-45

(164)

PI Output 2 Monitor

Minimum

Sets the minimum display value at zero speed.

This function is effective when b5-42 is set to 0 (Linear output mode).

Note:

Used for U5-14 and U5-15 only.

Default: 0

Min.: 0

Max.: 999.9

b5-46

(165)

PID Units Selection

Sets the display units for parameter b5-19, and monitors U5-01, U5-04 and

U5-99

0: WC (Inch of water)

1: PSI (Pounds per square inch)

2: GPM (Gallons per minute)

3: F (Degrees Fahrenheit)

4: CFM (Cubic feet per minute)

5: CMH (Cubic meters per hour)

6: LPH (Liters per hour)

7: LPS (Liters per second)

8: Bar (Bar)

9: Pa (Pascal)

10: C (Degrees Celsius)

11: Mtr (Meters)

12: Ft (Feet)

13: LPM (Liters per minute)

14: CMM (Cubic meters per minute)

15: “Hg (Inches of Mercury)

25: None

Default: 0

Range: 0 to 15; 25

b5-47

(17D)

Reverse Operation Selection

2 by PID Output

0: Zero limit when PID output is a negative value.

1: Reverse operation when PID output is a negative value

(Zero limit if the reverse operation is prohibited by b1-04).

Default: 1

Range: 0, 1

b5-89

(B89)

Sleep Method Selection

Determines how the drive sleeps and wakes-up when using PID.

0: Standard

1: EZ Sleep/Wake-up

Default: 0

Range: 0, 1

b5-90

(B90)

<1>

EZ Sleep Unit

Sets the unit, range, and resolution of parameters b5-91 and b5-92.

0: Hz

1: RPM (number of motor poles must be entered)

Default: 0

Range: 0, 1

b5-91

(B91)

<1>

EZ Minimum Speed

Sets the PID minimum speed and integral lower limit.

The internal value is lower limited to the higher setting between b5-34 and

d2-02.

Default: 0.0 Hz

Range: 0.0 to

400.0 Hz
or 0 to 24000 RPM

<2>

b5-92

(B92)

<1>

EZ Sleep Level

The drive will go to sleep when the drive output frequency (or speed) is at or

below this level for the time set in b5-93.

This parameter is internally lower limited to b5-91 (EZ Min Speed) + 1Hz.

Default: 0.0 Hz

Range: 0.0 to

400.0 Hz
or 0 to 24000 RPM

<2>

b5-93

(B93)

<1>

EZ Sleep Time

The drive will go to sleep when the drive output frequency is at or below the

level set to b5-92 for the time set in this parameter.

Default: 5.0 s

Min.: 0.0

Max.: 1000.0

B.2 b: Application

YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide

189

B

Parameter List