F3200 Installation & Programming Manual

Programming System Configuration

Issue 2.7

5 July 2001

Page 7-7

MODE (CONTINUED)

Switches in additional pull up resistor to +22V in Alarm.

Suits detectors with high alarm current requirement or remote LED indicators.

(Refer to Appendix A2).

Mode 3

Low Current

680 Ohm pull up resistor to +22V supply.

10k EOL.

Suits high resistance, low current circuit e.g. sub-indicator panel monitoring.

Mode 4

Tamper

680 Ohm pull up resistor to +22V supply.

Requires EOL002Z active EOL.

Suits supervision of "tamper-protected" sprinkler valves.

Mode 5

Disabled

Current limit and pull up disabled.

No EOL required.

Suits unused AZCs (saves quiescent current).

7.2.4 TIME

DELAYS

The standard time delay on any change of state is 2.3 secs (2.0-2.6 secs) i.e. to Alarm, to

Fault, to Normal. During this time the input conditions are continually read (and debounced).

The input must be continuously in the new state for the duration of the time delay to cause a

change of state.

There are two programmable time delays assigned to each circuit i.e. delay into alarm Delay

1 (D1) and delay out of alarm Delay 2 (D2). One, or both of these are also used to generate

the other time delay types as follows, AVF = Alarm Verification, RAD = Return Air Detector,

SAD = Supply Air Detector.

Note that the actual time delay also depends on the new condition (i.e. alarm or instant

alarm). The operation of the SAD type was changed in V2.09 software.

Delay Type

Delay To Alarm

Delay to Normal

(applies to cct not zone)

1 Std

Inst Alarm 2.3

2.3

Alarm 2.3

2.3

2 AVF/RAD

Inst Alarm 2.3

2.3

Alarm (AVF/RAD sequence

2.3

using D1)

3 SAD

For V2.08 or earlier

Inst. Alarm 2.3

2.3

Alarm (AVF/RAD sequence

D2

Using D1)
For V2.09 or later

Inst. Alarm 2.3

2.3

If D1 is zero (default) the into

D2

Alarm time is 2.3 seconds

If D1 is non-zero the delay into

Alarm is AVF (using D1).