Ndu quiescent and alarm currents – Tyco F3200 User Manual

Page 35

Advertising
background image

Document No: LT0122

F3200 Installation & Programming Manual

System Specifications

Issue 2.7

5 July 2001

Page 3-7

3.3.5.2

NDU Quiescent and Alarm Currents

Slimline NDU (FP0714/FP0773/FP0774

4

)

Operating Voltage

:

24Vdc (18-28V)

Termination

:

For up to 2.5sqmm TPS

Quiescent

Alarm

Current Consumption :

25mA

80mA

Full cabinet NDU (FP0715)

Quiescent

Alarm

Current Consumption (Aust mode)

1

70mA

165mA

Current Consumption (NZ mode)

2

85mA

150mA

1.

Includes controller, MAF/PSU, energised standby relay, PA0773 RS485 Bd, LCD
backlight off in quiescent state.

2.

Includes controller, MAF/PSU, NZ Display Extender, energised standby and alarm
relays, PA0773 RS485 Bd. LCD backlight off in quiescent state.

3.

Refer to Section 3.3.5.1 for additional module currents.

4.

For FP0774 the I-Hub currents must be added.