System Specifications

Issue 2.7

5 July 2001

Page 3-11

ICL+R = Current sourced through current limit and pull up resistor

IAV = Current available to detectors with EOLR fitted

IAV = ICL+R - IEOLR

GRAPH 3.4.3

AZC CURRENT VS VOLTAGE MODE 2 (HIGH CURRENT)

A short circuit at the end of an 800 Ohm line will give a B2 (Detector Operated) alarm.

A short circuit at the end of a 2k Ohm line will give a B3 (programmable) condition.

GRAPH 3.4.4

ACZ CURRENT VS VOLTAGE MODES 3 & 4 (LOW CURRENT & TAMPER)