System structure, Pcb modules, System structure -10 – Tyco F3200 User Manual

Page 24: 3 system structure

Advertising
background image

F3200 Installation & Programming Manual

Document No: LT0122

System Description

Page 2-10

5 July 2001

Issue 2.7

2.3 SYSTEM

STRUCTURE

2.3.1 PCB

MODULES

The 6 printed circuit boards which are used in an F3200 are as follows:

Controller/Display

Mounts on 4U inner door.

Includes:

LCD, status LEDs and buzzer

keypad connection

5Vdc supply

voltage monitors for battery charger

microprocessor & memory

serial I/O bus control for all other modules

reference voltage generation for I/O modules

UARTs and serial port electronics

real time clock calendar integrated circuit

FRC connection to other modules.

MAF/PSU

Mounts on cabinet rear wall.

Includes:

battery charger/PSU

22V regulator for detector circuits

Brigade & Ancillary relays and supervision circuitry

MCP & door switch inputs

screw terminals (most demountable) for field wiring

FRC connection to other modules.

8 Zone Module

Mounts on cabinet rear or in cardframe.

Includes:

electronics to I/F to 8 Alarm Zone Circuits (AZCs)

8 open collector auxiliary outputs

demountable screw terminals for field wiring

FRC connection to other modules.

8 Relay Module

Mounts on cabinet rear or in cardframe.

Includes:

8 relays and supervision circuitry

demountable screw terminals for field wiring

FRC connection to other modules.

16 Zone LED Display

Mounts on 7U inner door.

Includes:

16 sets of 3 LEDs

electronics to control the LEDs (serial bus)

Advertising