Links on pcb modules, Controller/display, Maf/psu – Tyco F3200 User Manual

Page 65: 8 relay module, 16 zone led display, Links on pcb modules -11, 4 links on pcb modules

Advertising
background image

Document No: LT0122

F3200 Installation & Programming Manual

Configuring a FIP

Issue 2.7

5 July 2001

Page 5-11

5.4

LINKS ON PCB MODULES

5.4.1 CONTROLLER/DISPLAY

Apart from E2INIT (SW1) and DATABASE WRITE PROTECT/ENABLE (Lk7) all links on the

Controller Display are factory set. (These configure the pcb for memory chips used, other

functions, and type e.g. as a FIP Controller or an RZDU Controller).

SW1 and Lk7 are described in Section 6.3.1.

5.4.2 MAF/PSU

Of the 4 links on the MAF/PSU, 3 are for field adjustment as follows:

Lk2-Lk4

Bells/ANC 3

-

Fitted in factory to provide switched 24V output.

(Bells+, Bells-).

-

Snip all 3 for clean changeover contacts (NO,

COM, NC).

Note that Lk2-Lk4 must remain fitted if Bells supervision is required (No links are required for

Ancillary Relay 1, 2 supervision).

One is for factory configuration as follows:

Lk1

Master/RZDU

-

Fitted for Master.

-

Snipped for RZDU (3-wire isolated connection

to FIP).

5.4.3 8

RELAY

MODULE

The 8 three position links (Lk1-Lk8) select load supervision for each relay.

U <-> unsupervised (voltage free)

S <-> supervised

The default setting (factory set) is unsupervised. Note that in addition to shifting the

minijump for supervision, supervision must be enabled during programming.

5.4.4

16 ZONE LED DISPLAY

The last Display Bd in the chain (i.e. in furthest left position as viewed from the front)

requires the minijump provided to be fitted to Lk1.