F3200 Installation & Programming Manual

Document No: LT0122

Programming

Page 6-28

5 July 2001

Issue 2.7

GLOBAL DATA (CONTINUED)

The following table indicates suitable settings:

COUNTRY/STATE

FORWARD

BACKWARD

ENABLE

D

MONTH

SUNDA

Y

HOUR

MONTH

SUNDA

Y

HOUR

NSW, ACT, VIC, SA

Y

10

L

2

3

L

3

TAS (1)

Y

10

L

2

3

L

3

NZ

Y

10

1

2

3

3

2

WA, NT, QLD (2)

N

-

-

-

-

-

-

NOTE: (1)

Tasmania may start Daylight Saving earlier at their discretion.

(2)

WA, NT and QLD do not have Daylight Saving.

Mains/Battery Options

Most of these options are available only in V2.07 or later software and are intended for

installations which have to meet the requirements of the Australian Standard AS4428.1

1998.

Mains fail = fault after 8 hours

If this is enabled, then when mains has been failed continuously for 8 hours a fault will be

signalled.

Charger fault monitor – if enabled, signals a fault when the charger is high or low.

Battery low monitoring – if enabled, a fault is signalled when a battery low voltage occurs.

For a slimline NDU with no MAF board, the battery very low threshold is used as the battery

low threshold. Battery low monitoring and battery connection tests are not required for

AS1603.4 but are required for AS4428.1.

Battery connection test – if enabled, the battery connection will be checked every 30

seconds by reducing the charger voltage.

Hourly battery capacity test – if enabled, a 60 second battery test will be done automatically

on the hour.

Daily battery capacity test – if enabled, a 40 minute battery test will be done automatically at

the start of the daily auto test or at 9am if there is no auto test. WARNING: older versions of

F3200 must have the battery test resistors R52, R53 removed from the MAF board if this test

is enabled.

Keys Enable

V2.06 or earlier software

V2.06 or earlier software allows two specific keys – BELLS ISOL and ANCIL ISOL- to be

programmed as enabled or disabled. When disabled, the key will be ignored but the isolate

functions that are normally accessible with these keys can be done using zones 193 to 197.