Current consumption, F3200 quiescent & alarm currents – Tyco F3200 User Manual

Page 34

Advertising
background image

F3200 Installation & Programming Manual

Document No: LT0122

System Specifications

Page 3-6

5 July 2001

Issue 2.7

3.3.5 CURRENT

CONSUMPTION

3.3.5.1

F3200 Quiescent & Alarm Currents

At 24Vdc battery supply, nominal currents:

Quiescent

Alarm (2 Zone)

FP0550, FP0551, FP0583, FP0712, FP0713

130mA

275mA

(notes 1-4)

8 Zone Module

- all AZCs disabled

4mA

- all AZCs enabled (notes 2-6)

82mA

97mA

Current per enabled AZC (note 3)

10mA

8 Relay Module

- all supervision disabled

4mA

- all supervision enabled

6mA

Current per relay on

11mA

MAF/PSU

- all relays off

9mA

Current per Ancillary Relay

(includes bells)

11mA

11mA

Current per Brigade Relay

16mA

16mA

22V Supply (supplies 8 Zones) max rating

800mA

Controller/Display

- LCD backlight off, status LEDs off

19mA

- LCD backlight on, status LEDs off

75mA

Current per status LED on

3mA

16 Zone LED Display

0mA

16mA/LED (steady)

RS485 network interface board PA0773

7.5mA

Total electronics and detector max rating 2000mA

Notes

1.

FP0550/551/583/712/713 currents include Controller/Display, MAF/PSU and 1 x 8ZM

with all ACZs enabled and with EOLRs (2K7 for mode 1 or 2).

2.

Quiescent current for an enabled AZC is for modes 1 or 2 (standard or high current)

and includes the 2k7 EOL, but not the detector current (up to 4mA detector current

per AZC).

3.

Quiescent current is only 2.5mA per AZC for mode 3 and 1mA for mode 4.

4.

Alarm current is for AZC mode 1, refer AZC specifications for other modes.

5.

The 8 Zone Modules (8ZMs) are supplied from the fused battery supply via the 22V

regulator which has a maximum rating. The 8 Relay Modules (8RMs) are supplied

directly from the fused battery supply.

6.

Quiescent and alarm currents do not include external loads e.g. door holders, bells,

etc.