F3200 Installation & Programming Manual

Document No: LT0122

Applications

Page 9-4

5 July 2001

Issue 2.7

CIRCUITS & ZONES (CONTINUED)

The option in Fig 9.1.3 A could be implemented by "tacking" the 560E resistor (or 6V8

Zener) onto the pcb. The 2 AZC option (Fig 9.1.4) could also be implemented by soldering

the extra resistor and wires onto the unused contact of the rotary switch on the pcb.

In all cases, "auto" is zone "normal".

OFF

┌──────────────o

│ AUTO ┌──┐

│ ┌─────o─────o──────────────────────┤ │+

╒╧╕ │ └──┘

6V8

│ │ ┌┴┐ ON o AZC

OR

└┬┘ 2K7│ │ │

560E

│ └┬┘ │ ┌──┐

└──────┴────────┴─────────────────────────┤ │-

└──┘

A.

WITH A ROTARY SWITCH, "ON" IS B1 (INSTANT), "OFF" IS B2 (ALARM).

OFF
o
AUTO

┌──┐

┌────────────o─────o──────────────────────┤ │+

┌┴┐ └──┘

2K7

│ │ ON o AZC

└┬┘ │

│ │ ┌──┐

└───────────────┴─────────────────────────┤ │-

└──┘

B.

WITH A ROTARY SWITCH, "ON" IS B1 (INSTANT), "OFF" IS FAULT.

OFF

┌──────────────o

│ AUTO ┌──┐

│ ──────o───┬──────────────────┤ │+

╒╧╕ │ └──┘

6V8

│ │ ON o ┌┴┐ AZC

OR

└┬┘ │ │ │2K7

560E

│ │ └┬┘ ┌──┐

└───────────────┴──────┴──────────────────┤ │-

└──┘

C.

WITH A CENTRE-OFF TOGGLE SWITCH, "ON" IS B1 (INSTANT), "OFF" IS B2

(ALARM).

FIG 9.1.3

FAN CONTROL SWITCH WIRING WITH SINGLE AZC