Document No: LT0122

F3200 Installation & Programming Manual

Network Programming

Issue 2.7

5 July 2001

Page 11-13

SID MENU ONE (CONTINUED)

If the F3200 is programmed to receive FFCIF events from a particular SID, then it is also

able to send Ack, Reset and Isolate commands for the event back to the originating SID

(providing that reset and isolate of remote alarms is also enabled - refer section 11.7 FFCIF

config).

5. TX CMD : (Yes/No)

If enabled this allows this panel to send commands to the selected SID. This includes zone

reset/isolate/test commands as well as system commands such as system test/battery

test/bell test. If disabled, this panel is still allowed to recall the status of zones from the

selected SID but not control them.

6. RX CMD : (Yes/No)

If enabled this allows this panel to receive and execute commands from the selected SID. If

disabled, commands received from the selected SID will be ignored but a recall of zone

status will still be permitted. NOTE :- this option does not affect FFCIF commands received

from another panel which will still be accepted, (if FFCIF TX alarms is enabled), even if the

RX CMD option here is disabled. (refer also section 11.7 FFCIF configuration).

11.4.2

SID MENU TWO

1. SID : (1-254)

Change the SID number that is being viewed/modified.

2. Use MAF relay data : (Yes/No)

If enabled, MAF data received from the selected SID will be used by this panel i.e. combined

with local MAF status and possibly MAF status of other SIDs and used to drive the brigade

signalling etc. Refer to section 11.2.2 for a description of network MAF status.

3. Use MAF totals : (Yes/No)

If enabled, the totals received from the selected SID are included in the totals shown on this

panel. If enabled, it also means that a non zero total received from the selected SID, (alarm,

fault or isolate), will cause the corresponding LED on the front panel to turn on. Also, if

enabled, the buzzer will turn on when a new MAF or system fault (as received in the MAF

status) is received from the selected SID. The buzzer will turn on if "use MAF totals" is

enabled even if "use MAF relay data" is disabled for the selected SID.

4. Status search : (Yes/No)

If enabled, a recall of off normal zones will include the selected SID in the search. If

disabled, an off normal recall will not search the SID but specific zones from that SID may

still be recalled using their network zone number.