F3200 Installation & Programming Manual

Document No: LT0122

Installation & Wiring

Page 8-10

5 July 2001

Issue 2.7

8.3 AZC

WIRING

Detectors must be installed and wired as per AS1670.1. Observe the requirements for

conductor type and size.

Connection to the particular MCPs, detectors or bases must be as specified by the

manufacturer. Similarly for remote LED connection.

AZCs must be wired as per Fig 8.3.1 with "In" of the first detector connected to the 8ZM, and

the EOLR to the "out" of the furthest detector.

Examples of illegal wiring are shown in Fig 8.3.3.

┌─────────────┐

│ 8ZM │

│ │

┌──────┐ ┌──────┐ ┌──────┐ │ │├─┤ │

┌────┼o+ +o┼──┼o+ +o┼── ─ ─ ─ ─ ─┼o+ +o┼──────────┼───┤│

O

│ + │

┌┴┐ │ │ │ │ │ │ │ │├─┤ CCTn │

EOL

│ │ │OUT IN│ │OUT IN│ │OUT IN│ ┌────┼───┤│O│ - │

└┬┘ │ │ │ │ │ │ │ │ │├─┤ │

└────┼o- -o┼──┼o- -o┼── ─ ─ ─ ─ ─┼o- -o┼─────┘ │ ││

O

│ │

└──────┘ └──────┘ └──────┘ │ │

└─────────────┘

FIG 8.3.1

CORRECT AZC DETECTOR WIRING

The Tyco SU0600 MCP may be used on a circuit that has detectors on it, so that activation

of the MCP does not reset the indication on any already activated detector. Wiring of the

SU0600 is shown in Fig 8.3.2. The zone must be programmed with B3 = Instant Alarm.

FIG 8.3.2

TYCO SU0600 CONNECTION