Default values for panel-link variables, Default values for panel-link variables -24, 12 default values for panel-link variables – Tyco F3200 User Manual

Page 234

Advertising
background image

F3200 Installation & Programming Manual

Document No: LT0122

Network Programming

Page 11-24

5 July 2001

Issue 2.7

11.12 DEFAULT VALUES FOR PANEL-LINK VARIABLES

Item

Parameters

Default

Network Setup

Local SID Number

1-254

0

Mode

Multidrop/Pnt to Pnt

Multidrop

NIC

Yes/No

No

RX Timeout

1-250 5 millisecs

2

TX Delay

1-250 5 millisecs

1

ACK Time

1-9999 millisecs

800

DUP Time

1-9000 millisecs

2000

Leading FF

0-250 characters

1

Trailing FF

0-250 seconds

1

Link TX

Yes/No

Yes

Link Tx Time

1-250 seconds

5

Link RX Time

1-250 seconds

50

Groups

Any combination of 1

[12345678]

to 8

ACK Broadcasts

Yes/No

No

Baud rate

300 up to 19200

9600

Retries

0-15

5

Slots

8, 16, 32

8

Mode B

0-7

3

ACK Bcasts Specific SID

0-254

0

Network SID Configuration (per SID)

Link RX

Yes/No

No

Log Events

Yes/No

No

RX FFCIF

Yes/No

No

TX CMD

Yes/No

No

RX CMD

Yes/No

No

Use MAF data

Yes/No

No

Use MAF totals

Yes/No

No

Status search

Yes/No

No

Network MAF Config

Refresh TX Time

1-250 seconds

20

Max COS rate

0-250 seconds

2

Receive net bells

control

Yes/No

No

Send net silence

Yes/No

No

Receive net silence

Yes/No

No

Network Command Config

ACK Time

1-250 seconds

10

Work Time

1-250 seconds

3

RX net time/date

Yes/No

Yes

TX net time/date

Yes/No

No

FFCIF Config

TX Alarms

Yes/No

No

Dedicated TX SID

0-254 (0=all)

0

RX Net ACK

Yes/No

No

TX iso/reset cmds

Yes/No

No

TX ack cmds

Yes/No

No

Advertising