Document No: LT0122

F3200 Installation & Programming Manual

Applications

Issue 2.7

5 July 2001

Page 9-31

4 TERMINAL ISOLATED REPEATER ALONE (CONTINUED)

GAS GROUP 11A OR 11B

GAS GROUP 11C

DETECTOR

CCT LENGTH

CCT LENGTH

TYPE

PART

BASE

QTY

1.0mm²

0.75mm²

QTY

1.00mm²

0.75mm²

HEAT

HEAT

HEAT

FW105

T54B

T56B

-

-

Z500N

-

40(M)

40(M)

NOTE 2 & 3

(68Ω TOT)

2km(R)

(68Ω TOT)

2km(R)

(100Ω)

NOTE 2 & 3

(68Ω TOT)

1.5km(R)

(68Ω)

1.5km(R)

(68Ω)

-

40(M)

40(M)

1.3km TOT

(130nF)

1.3km(C)

(130nF)

1.3km(C)

(130nF)

1.3km TOT

(130nF)

1.3km(C)

(130nF)

1.3km(C)

(130nF)

TABLE 9.4.5

MAXIMUM DETECTOR QUANTITY & CABLE LENGTH FOR 4 TERMINAL

REPEATER ALONE

Notes

1.

Circuit lengths quoted are from the isolator to the EOL. The length quoted is the

maximum for the corresponding quantity of detectors.

2.

Cable resistance shown is for the circuit, ie. both cables in the pair. The value of 34Ω

per km (return) is used for 1 mm².

3.

The maximum resistances shown for the fire wire circuits must include both cable

and fire wire (see table 9.4.2 and associated note 2).

4.

The letter in ( ) after the cable length, and the value in ( ) under the cable length

specify which parameter out of capacitance (C), inductance (L) and resistance (R)

provides the limitation, and what the limiting value is.

5.

The (M) after a detector quantity indicates the maximum quantity allowed per circuit.