Tyco F3200 User Manual

Page 44

Advertising
background image

F3200 Installation & Programming Manual

Document No: LT0122

System Specifications

Page 3-16

5 July 2001

Issue 2.7

MAF/PSU OUTPUTS (CONTINUED)

Option

1 Pole changeover contacts

Voltage-free

Snip Links Lk2, 3, 4.

Rating

ELV only

30V, 2Adc resistive

30V, 1Adc inductive

24V, 1.5Adc inductive bells

Operation

Programmable

Default

Active on any unisolated zone alarm

Supervision

On Bells +, - only

(ref 3.4.2)

Power Supply Outputs

0Vdc

Termination

1 non-demountable screw terminal

4sq mm max cable

2 demountable screw terminals

1.5sq mm max cable

1 2.8mm tab terminal (LED Display)

Battery Backed DC Supply

Rating

27.3Vdc nom.

(24V battery nom)

2Adc, fused.

+VBF1

Termination

1 non-demountable screw terminal

4sq mm max cable

1 demountable screw terminal

1.5sq mm max cable

+VBF2

Termination

1 non-demountable screw terminal

4sq mm max cable

1 demountable screw terminal

1.5sq mm max cable

1 2.8mm tab terminal (LED Display)