Tyco F3200 User Manual

Page 98

Advertising
background image

F3200 Installation & Programming Manual

Document No: LT0122

Programming

Page 6-32

5 July 2001

Issue 2.7

The following table lists all of the programmable non-network parameters. The defaults

listed are for Australian operation. The previous section lists items that have defaults

specific to New Zealand operation.

Item

Options

Default

Access Codes

Qty 1-10

1 (User 0)

6 Digits

000000 (User 0)

Autotest Time

Time

9:00am

Autotest Inhibit

Dates For No Test

Stat Holidays, weekends

Autotest Alarm

Alarm Test Yes/No

No alarm test

FIP MCP Zone, Disable

Zone 1, Enabled

FFCIF Type

2/3

Type 3

FFCIF Mode

MAF Zones Only/

MAF Zones Only

All Zones/Disabled

FFCIF RZDU Remote Ack

Enabled/Disabled

Enabled

FFCIF Auto Ack

Enabled/Disabled

Disabled

FFCIF Alarm Bells

Enabled/Disabled

Disabled

FFCIF Display Cause

Enabled/Disabled

Disabled

FFCIF always flash non-maf

Enabled/Disabled

Disabled

alarm LEDs
FFCIF always send non-maf alarm

Enabled/Disabled

Disabled

to RDU
All zones isolated = Standby

Standby operate/not operate

operates

Brig Test

Operate/Not MAF Alarm Relay Operates Alm Relay (V2.07

or earlier)
No operation (V2.08 or later)

Printer

Lines Per Page

60

Baud Rate

9600

Print Relay Operates

Enabled

Event printing

Enabled

Printer and history

Event type selections for
history & printer -
- zone, system, sys run,
circuit, point, relay.

All types enabled

Coder (NSW Cty)

Disabled/1-6 Pulses

Disabled

Daylight saving start

Start time/date/diff

Last SUN, OCT, 2am, 1 hr

Daylight saving end

End time/date/diff

Last SUN, MAR, 3am, 1 hr

Mains 50/60Hz

50/60Hz

50Hz

Mains fault is fault after 8 hours

Enable/Disable

Disabled

Battery low monitor

Enable/Disable

Disabled

Battery connection monitor

Enable/Disable

Disabled

Hourly battery test

Enable/Disable

Disabled

Daily 40 minute battery test

Enable/Disable

Disabled

Charger high/low = Fault

Enable/Disable

Disabled

Alarm buzzer

Enable/Disable

Enabled

Zone fault buzzer

Enable/Disable

Enabled

System fault buzzer

Enable/Disable

Enabled

Buzzer for non-MAF zone faults

Enable/Disable

Disabled

Fault sounder after 8 hours fault

Enable/Disable

Disabled

Fault sounder after 8 hours isolate

Enable/Disable

Disabled

TABLE 6.4.1

PROGRAMMABLE PARAMETERS

Continued .......

Advertising