Mains wiring – Tyco F3200 User Manual

Page 147

Advertising
background image

Document No: LT0122

F3200 Installation & Programming Manual

Installation & Wiring

Issue 2.7

5 July 2001

Page 8-9

FIG 8.2.2

GOOSENECK CABLING

8.2.2 MAINS

WIRING

The mains (240Vac) supply must be connected in accordance with AS1670.1 and AS3000

regulations.

Ensure the mains cables to the FIP are isolated at the Distribution Board
before connecting to the FIP.

The mains cable connects to the 3 way terminal block mounted to the cabinet rear behind

the mains cover.

(a)

Remove the mains cover with a Pozi screw-driver.

(b)

Shape the mains cable to fit through the grommet in the slot in the top of the cover,

cut to length and strip only 20mm of the PVC cable sheath.

(c)

Connect the wires:

blue (black) to N

brown (red) to A

green/yellow (green) to E

Take care when stripping not to "nick" wires.

(d)

Cable tie the cable to the cabinet.

(e)

Refit the mains cover .