Net ffcif configuration, Net ffcif configuration -16, 7 net ffcif configuration – Tyco F3200 User Manual

Page 226

Advertising
background image

F3200 Installation & Programming Manual

Document No: LT0122

Network Programming

Page 11-16

5 July 2001

Issue 2.7

11.7 NET

FFCIF

CONFIGURATION

This determines whether FFCIF alarm events are sent onto the network, and can provide an

extra level of confirmation that alarm events have been received by one or more devices on

the network. FFCIF alarms sent onto the network will be entered into the FFCIF alarm list of

another panel only if the panel sending the alarm has at least one group in common with the

panel receiving the alarm (refer section 11.3.3 groups). For F3200 and NDUs the SID list

programming also determines whether FFCIF alarms received from other panels are entered

into the FFCIF alarm list of this panel.

Alarms which are entered into the local FFCIF alarms list may be either local alarms or

alarms which have come from other panels. In both cases, these alarms can be

acknowledged from either the local panel or from a remote panel but it is possible to disable

the acceptance of acknowledgments which come from remote network devices and to force

all FFCIF alarms to be acknowledged locally - see item 3 "Remote ACK" below.

If FFCIF auto ack is enabled, (refer section 6.4.4), any alarms which are entered into the

local FFCIF alarm list (i.e. both local alarms and remote alarms) are automatically flagged as

"acknowledged", but this does not result in any acknowledge indication or command being

sent onto the network.

Options under FFCIF1

1. TX alarms : (Yes/No)

If enabled, any FFCIF alarm that is entered into the FFCIF list of this panel will also be sent

onto the network. Setting this to enabled also determines whether this panel accepts FFCIF

commands from other panels to acknowledge, reset or isolate FFCIF alarms. NOTE :- an

FFCIF command is not the same as a zone command. If FFCIF alarms are not being

transmitted onto the network then FFCIF commands will not be accepted from other panels

but zone/system commands etc. may still be accepted depending on the RX CMD option

programmed in the SID list of this panel. Refer also section 11.4.2 SID list RX CMD option.

Note, an FFCIF command is either an acknowledge, reset, or isolate command which is

initiated when the associated ACK, RESET or ISOLATE key is pressed from within FFCIF

mode i.e. when the FFCIF alarm list is being displayed. Zone commands or system

commands are initiated using the ZONE or SYSTEM keys.

2. Dedicated TX SID : (0-254)

If this parameter is zero, then any FFCIF alarms that are transmitted onto the network, ( i.e.

TX alarms enabled ), will be broadcast, (i.e. received by all devices on the network), and

each device can individually decide, ( according to group programming and SID list

programming), whether to enter that FFCIF alarm into its own FFCIF alarm list.

If this parameter is non zero then FFCIF alarms will not be broadcast onto the network but

will be sent specifically to the SID specified by this number. No devices on the network other

than the specified SID will receive FFCIF alarms sent by this panel.

If FFCIF alarms are broadcast onto the network, then confirmation of delivery can be

provided by setting "acknowledge of broadcasts" enabled (refer section 11.3.1 NIC option).

If FFCIF alarms are directed to one specific SID then that SID will acknowledge receipt of

the alarm and acknowledge of broadcasts is not involved. If acknowledge of broadcasts is

not enabled, (or this device is doing the acknowledge of broadcasts), and only one other

device is required to receive FFCIF alarms from this SID, then it is preferable to set the "TX

dedicated SID" parameter here to a specific SID number.

Advertising