Leds – Tyco F3200 User Manual

Page 171

Advertising
background image

Document No: LT0122

F3200 Installation & Programming Manual

Applications

Issue 2.7

5 July 2001

Page 9-7

CIRCUITS & ZONES (CONTINUED)

R5 = Z15D + Z15N.Z5A.^ (Z1:4(1)A+Z6:10(1)A)

Note also, that if the interposing relay (fan control input) is 24V at less than 100mA then an

open collector (O/C) may be used as per circuit 1 of 1945-1-1/4 following.

9.1.4 LEDS

The 3 LEDs may be: switched directly as per circuits 1 and 2 of 1945-1; driven off 3 open

collector (O/C) outputs or driven off 2 O/Cs with a Zener diode as shown in Fig 9.1.6 and

1945-1-3. Note that where the FIP has a number of detector circuits, the open collector

outputs associated with these AZCs may be used for driving the AS1668 LEDs and so it

doesn't matter if the AS1668 panel requires more open collectors than circuits.

+VBF

─┬─

│ 3K3 ┌──┐

RUN

├───────>├────█████────────┤ │ OC1

│ Red └──┘

│ 3K3 ┌──┐

FAULT

├───────>├────█████────────┤ │ OC2

│ Yellow └──┘

│ 3K3 ┌──┐

STOP

└───────>├────█████────────┤ │ OC3

Green

└──┘

A.

THREE OPEN COLLECTOR O/PS PER FAN (Ref 1945-1-4).

+VBF

─┬─

│ 3k3 RUN ┌──┐

├────█████───┬───>├────────┤ │ OC1

│ │ Red └──┘

│ STOP

Green

│ ╒╧╕

│ │ │3V9 ZENER

│ └┬┘

│ ─┴─

│ 3K3 0V FAULT ┌──┐

└────█████───────>├────────┤ │ OC2

Yellow

└──┘

B.

TWO OPEN COLLECTOR O/PS PER FAN (Ref 1945-1-3).

For other LEDs (eg. Chrome Bezel LEDs) a lower value (higher current) resistor may be

required.

FIG 9.1.6

WIRING OF FAN CONTROL LEDS

Advertising