Tyco F3200 User Manual

Page 89

Advertising
background image

Document No: LT0122

F3200 Installation & Programming Manual

Programming

Issue 2.7

5 July 2001

Page 6-23

GLOBAL DATA (CONTINUED)

For V2.07 and later software

1:Auto test; 2:FIP MCP; 3:FFCIF options; 4:All zones isolated; 5:More

3:FFCIF options provides the following:

FFCIF zones (MAF only, all, none)

Auto Ack enable/disable

FFCIF type 2/3

Remote Ack enable/disable

FFCIF alarm = bells on enable/disable

Display cause by default enable/disable

Always flash non-MAF alarm LEDs – enable/disable

Always send non-MAF FF alarm to RDU – enable/disable

5:more selects the following menu

1:Brigade test relay activate; 2:Printer setup;

3:Country coder; 4:more

4:More selects the following menu

1:Daylight saving start; 3:Mains/battery

2:Daylight saving end; 4:More

3:Mains/battery provides the following

Mains frequency 50/60Hz

Mains fail action

Battery low monitor enable

Battery tests enable

Charger fault monitor

4:More selects the following menu

1:Keys enable; 2:Remote sounder silence

3:Buzzer mode; 4:New Zealand mode options

The above items are described in more detail in the following pages.

Auto Test

The automatic test of memory, AZCs, etc, occurs at a programmed time every day except on

weekends or programmed inhibit dates. This is to reduce the cost of callouts should the

auto-test discover a "fault". Only the basic statutory holidays, 25/12, 26/12, 01/01, 02/01 &

weekends are inhibited by default. Other state/company specific ones should be added.

Note that the default programming does not include an alarm test of each AZC (zone) and to

disable the Auto Test completely set the Auto Test start time to 24:00:00.

FIP MCP

The default mapping for the FIP MCP is to zone 1, but any configured zone may be selected.

Note that in "special" FIPs which do not have an MCP fitted it should be disabled to prevent

Fault occurring on the zone it is mapped to. To disable it, select zone 0.

WARNING

It is possible to map the FIP MCP to a zone which is not configured.

This would not be displayed or logged and the MCP is disabled.

Advertising