F3200 Installation & Programming Manual

Document No: LT0122

Applications

Page 9-28

5 July 2001

Issue 2.7

FIG 9.4.3.3

F3200 WITH ZAU401 & 4 TERMINAL IS REPEATER

Programming & Limitations

The circuit should be programmed as Mode 1 (standard). Voltage bands B1 and B3 can be

left at default, though it is better to program B1 as fault. Voltage band B3 is not generated

by a ZAU401 so can be left at the default setting (which is “normal” for V1.XX software and

“instant alarm” for V2.XX software).

Note that all alarms from the ZAU401 will give voltage band B2 i.e. the FIP cannot

differentiate between MCP and detector operation, and voltage B1 represents a short on the

circuit between the FIP and the ZAU401 (i.e. internal wiring fault).

Detector quantity and circuit length limits are shown in Table 9.4.4.

1 BATT+

2 ZONE+
3 EOL+

4 EOL-

5 ZONE-

6 BATT-

T+ 3

TC 2

T- 1

ZAU401 (Rev 2)

(PA0838)

EOL*

To Panel
Zone Circuit

+

-

+ -

Panel
24V

{

KHD0_

OR

KFD0_

OR

MTL5061

+

-

Ex DETECTOR

EOL

3k9

5%

* EOL to suit Panel

SAFE AREA HAZARDOUS AREA

4-Terminal Isolating

Repeater

Ex DETECTOR