Output specifications, 8 zone module outputs, 8 relay module outputs – Tyco F3200 User Manual

Page 42: Output specifications -14, 5 output specifications

Advertising
background image

F3200 Installation & Programming Manual

Document No: LT0122

System Specifications

Page 3-14

5 July 2001

Issue 2.7

3.5 OUTPUT

SPECIFICATIONS

3.5.1

8 ZONE MODULE OUTPUTS

Type

Darlington open collector

Switch to 0V

Voltage Rating

28.5V max, "off" state

1V max @ 30mA, "on" state

1.1V max at 100mA

Current Rating

100mA max per O/P, 0.6A max per module

1A max per FIP.

Transient Protection

Allows external wiring

Terminations

8 Way demountable screw terminal

1.5sq mm max. cable

Operation

Programmable

Default

O/C 1 = Zone 1 Alarm

O/C 2 = Zone 2 Alarm

etc.

3.5.2

8 RELAY MODULE OUTPUTS

Form

1 Pole changeover contacts

Voltage-free when unsupervised

Termination

Demountable screw terminals

1.5sq mm max cable

Rating

ELV only

30V, 2Adc resistive

30V, 1Adc inductive

Note

The relays are 2 pole, with the second pole terminated on pcb pads.

Operation

Programmable

Supervision

Ref 3.4.4.

Looping Terminals

2 Sets of 4 joined

voltage-free terminals per module